Optional Modules Installation Procedure
RP-1001 15150:F 05/24/2001 21
7UDQVPLWWHU0RGXOH²;70
Polarities shown in activated positions. The wiring of this module must follow the requirements as
specified under UL Power-limited Wiring Requirements in Section 2.2.
Push the Disconnect switch down to prevent unwanted activation of the Municipal Box during test-
ing of the control panel. The Disconnect LED will remain illuminated while the Municipal Box is
disconnected. The System Trouble LED will indicate disconnected and/or Open Circuit conditions
on the Municipal Box.
Cutting the TBL jumper will allow the alarm reverse polarity circuit to open on trouble, if no alarm
exists.
Note: Remote Alarm, Remote Trouble and Municipal Box wiring can leave the building.
Note: This module is not suitable for transmitting reverse polarity Supervisory Signals.
`
`
`
TBL Jumper
Disconnect LED
Disconnect Switch
Remote Alarm
Remote Trouble
No Connection
Municipal Box*
* Dummy load terminals
6 and 7 (4.7K, 1/4 W
resistor) if Municipal
Box is not connected.
Power-limited Circuit
Non-Power-limited Circui
t