System Operation Control Switches
28 RP-1001 15150:F 05/24/2001
&RQWURO6ZLWFKHV
7RQH6LOHQFH
Acknowledge alarms, troubles and supervisories. The
panel has alarm and trouble resound with LED flash of
new conditions. The flashing trouble LED(s) illuminate
steadily on TONE SILENCE and the piezo turns off. A
second trouble will resound the piezo. Trouble condi-
tions are self-restoring. Alarms latch and require RESET
to clear. Unless the unit is set for non-latching supervi-
sory service, supervisories latch and require RESET to
clear. The piezo has three tones for different conditions;
see Piezo in Section 3.4.
$ODUP6LOHQFH
Acknowledge for alarms and supervisories. The
ALARM SILENCE switch will silence the local piezo,
change any flashing alarm LEDs to steady, and turn off
the notification circuits (not the Releasing Circuits). The
ALARM SILENCE LED will illuminate. Alarm
silence is a latching function and requires a RESET to
clear.
Note: Releasing Circuits will turn off only if Discharge
timer criteria is satisfied; see Setting Mode of
Operation in Section 2.10.
$ODUP$FWLYDWH
The ALARM ACTIVATE switch may be used to activate
Notification Appliance Circuits. ALARM ACTIVATE
also activates the System Alarm relay. ALARM ACTI-
VATE is a latching function. Pressing ALARM
SILENCE silences the notification circuits and System
Alarm Relay and lights the Alarm Silenced LED. Press-
ing RESET returns the system to normal.
6\VWHP5HVHW
The RESET switch breaks power to all initiating circuits,
four-wire smoke power and optional boards and will
clear any activated output circuits. If any alarm or trou-
ble still exists after reset, they will reactivate the panel.
Holding RESET down will perform a LAMP TEST
function and will activate the piezo sounder.
=RQH6WDWXV/('V
The alarm and/or trouble LED(s) will flash until the event(s)
has been acknowledged (TONE or ALARM SILENCE), at
which point the LED(s) will illuminate steadily.
;37/FGU
Alarm LED
Trouble LED
Alarm LED
Trouble LED
Alarm LED
Trouble LED
(Not used)
Trouble LED
=21(
=21(
:$7(5)/2:
683(59,625<