System Operation Last Event Recall
30 RP-1001 15150:F 05/24/2001
/DVW(YHQW5HFDOO
Last Event Recall allows the user to display the previous panel status. The Last Event Recall makes
use of the four panel switches as follows:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press (in sequence) the RESET switch, the
ALARM ACTIVATE switch, and then the ALARM SILENCE switch.
3. LEDs will light to indicate the last event recorded in the panel’s buffer.
4. Release the TONE SILENCE switch to return to normal operation.
To clear the Last Event buffer, press RESET twice.
6SULQNOHU6XSHUYLVRU\7UDFNLQJ
The Initiating Device Circuit for sprinkler supervisory zone can be programmed for tracking opera-
tion; latching operation is the default setting. Canadian regulations require latching operation.
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch,
then the ALARM ACTIVATE switch, and finally the ALARM ACTIVATE switch again.
3. Release the TONE SILENCE switch.
If both primary and secondary power sources are removed from the system, this setting will be lost.
When power is restored, supervisory will default to latching operation.
1RQ6LOHQFHDEOH6HUYLFH
Notification Appliance Circuit #1 can be programmed as non-silenceable by following these steps:
1. Press and hold in the TONE SILENCE switch.
2. With the TONE SILENCE switch held in, press in sequence the ALARM SILENCE switch,
then the ALARM ACTIVATE switch, and finally the ALARM SILENCE switch again.
3. Release the TONE SILENCE switch.
If both primary and secondary power sources are removed from the system, these settings will be
lost. When power is restored, Notification Appliance Circuit #1 will default to silenceable
operation.
6\VWHP(YHQWV
6WDQGE\&RQGLWLRQ
Green LED (AC power on) will be illuminated. All other LEDs (trouble and alarm) are off.
6\VWHP7URXEOH&RQGLWLRQ
Interruption of any of the electrically supervised circuits will illuminate the System Trouble LED.
The Trouble Relay Contacts will transfer. The piezo (local buzzer) will sound: one second on, one
second off, and repeating until silenced. Silence the piezo by pressing the tone silence switch. The
panel will remain in the trouble state until the trouble condition has been cleared and the panel
reset.
6LQJOH=RQHLQ$ODUP&URVV=RQH&RQGLWLRQ
Upon actuation of a single-zone initiating device, a red alarm LED will illuminate to indicate
whether Zone 1 or Zone 2 is in alarm.
In addition to the LED, a single-zone alarm will activate the Alarm Relay; the piezo and remote