Product Description Features
6 RP-1001 15150:F 05/24/2001
Section 1 Product Description
The Notifier RP-1001/1001E Fire Alarm Control Panel has been designed as a control center for
single- and dual-hazard deluge and preaction applications. The RP-1001/1001E is a feature-packed
control unit suitable to perform detection and control functions associated with the release of water-
based fire protection systems. The panel is designed for maximum reliability with 100% solid state
circuitry and isolated relay contacts for outside interfacing. The panel features programmable
options to allow on-site customization of the unit for various operating configurations.
The RP-1001/1001E is supplied complete with backbox, hinged door, control switches, and
indicator LEDs. The RP-1001 is a 120 VAC fire alarm control panel. The RP-1001E is an export
version of the RP-1001 that runs on 220/240 VAC. The RP-1001C is a 120 VAC control unit that
functions according to the requirements of Underwriters Laboratories of Canada (ULC). An
integral standby battery system, with charger, is provided. In case of commercial AC power inter-
ruption, automatic switchover to the battery system will provide power to the panel for a minimum
of 24 hours.
)HDWXUHV
* Applications which require the 411UDAC, the NOTI-FIRE 911AC, or the Potter EFT-C are not
FM approved.
&LUFXLWV
,QSXW&LUFXLWV
Manual Release/Detector Circuit 1 (Style B/D)
Detector Circuit 2 (Style B/D)
Waterflow (Style B/D)
Supervisory (Style B/D)
Microprocessor-controlled
Alarm and trouble resound
Four Style B/D Initiating Device Circuits
Two Style Y/Z Notification Appliance
Circuits
Two Style Y Releasing Circuits
General alarm and trouble relays
Optional module for 4 zone/function relays
(4XZM)
Optional transmitter module (4XTM).
Optional volt/amp meter module (4XMM)
Optional supervised remote annunciator
(RZA-4X). Requires LED Interface
Module (4XLM)
Optional digital communicator (411UDAC,
NOTIFIRE 911AC).*
Designed for sprinkler standards NFPA 13,
15, and 16.
Disable/enable controls per initiating zone.
Last Event Recall
Battery/Earth fault supervision
Fuse protection on all Notification/Release
Circuits
RMS regulated output power, 2.25 amps
7 amp-hour (AH) to 18 AH battery options,
up to 90 hours standby
Resettable and nonresettable regulated
power outputs
Extensive transient protection
Watchdog timer to supervise
microprocessor
Output circuits protected against false
activations
Slide-in zone identification labels
Steel cabinet 14.5 in. wide (368.3 mm) by
16 in. high (406.4 mm) by 5 in. deep
(127 mm)
Dead-front dress panel option (DP-4X)
(Required for Canadian applications)
Trim ring for flush mount between 16 in.
(406.4 mm) center studs (TR-4XR)
Cross-zone (double-interlock) option
Municipal Box output.
Interface Module (4XLM)
Dual hazard operation
Adjustable discharge timer