Installation Procedure Setting Mode of Operation
24 RP-1001 15150:F 05/24/2001
6HWWLQJ0RGHRI2SHUDWLRQ
Select operating mode by setting the DIP switches on SW1; basic programming options are shown
in this section. After any changes are made to the configuration switches, the panel must be reset.
For Canadian use, refer to “Sprinkler Supervisory Tracking” in Section 3.8.
%DVLF3URJUDP
Select the desired mode of operation and set SW1 DIP switches 1 and 2 per the appropriate column.
1
2
3456
O
N
1
2
34
5
6
O
N
Battery Fail LED Ground Fault LED Micro Fail LED
Switch 6: Not used
;53',36FGU
DIP Switches for Basic Programming
Switch 1: Cross Zone
Switch 2: Dual Hazard
DIP Switches for Setting Discharge Timer
Switch 3: Discharge Timer
Switch 4: Discharge Timer
Switch 5: Discharge Timer
Mode #1
Single Hazard
Two Zone
Mode #2
Single Hazard
Cross Zone
Mode #3
Dual Hazard
Combined Release
Mode #4
Dual Hazard
Split Release
Outputs 1 and 3:
Activated by an alarm
on
either
Zone 1
or
2
.
Output 1:
Activated by an alarm
on
either
Zone 1
or
2
.
Output 1:
Activated by an alarm
on
either
Zone 1
or
2
or
a waterflow alarm
on
Zone 3.
Output 1:
Activated by an alarm
on
either
Zone 1
or
2
or
a waterflow alarm
on
Zone 3.
Output 2:
Activated by a
waterflow alarm on
Zone 3.
Output 2:
Activated by a
waterflow alarm on
Zone 3.
Output 2:
Activated by a
supervisory condition
on
Zone 4.
Output 2:
Activated by a
supervisory condition
on
Zone 4.
Output 4:
Activated
by a supervisory
condition on
Zone 4.
Output 3:
Activated
by alarms on
both
Zone
1
and
Zone 2.
Outputs 3 and 4:
Activated by an alarm
on
either
Zone 1
or
2
.
Output 3:
Activated by an alarm
on
Zone 1.
Output 4:
Activated
by a supervisory
condition on
Zone 4.
Output 4:
Activated
by an alarm on
Zone 2.
Note: Outputs 1 and 2 refer to Notification Appliance Circuits. Outputs 3 and 4 refer to
Releasing Circuits. Zones 1 and 2 refer to Initiating Device Circuits 1 and 2.