NFPA 72 Signalling Systems for Central Station Service — 911AC NFPA Standard-Specific Requirements
RP-1001 15150:F 05/24/2001 35
%1)3$6LJQDOOLQJ6\VWHPVIRU&HQWUDO6WDWLRQ6HUYLFH
² $&
3URWHFWHG3UHPLVHV8QLWDQG5HPRWH6WDWLRQ3URWHFWLYH6HUYLFH
NOTI-FIRE 911AC DACT* for connection to a Central Station Receiver or Protected Premises
Receiving Unit. This unit must be installed as illustrated below. If the NOTI-FIRE 911AC is not
mounted in the control panel’s backbox, all connections must be in conduit, less than 20 ft.
(609.6 cm) in length in the same room.
* This application using the NOTI-FIRE 911AC is not FM approved.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
1
2
4
6
7
8
9
10
11
12
3
5
1
2
5
6
7
8
9
10
12
13
14
15
16
17
3
4
11
12 VAC , 20V A, 60 Hz or +24 VD C
12 VAC , 20V A, 60 Hz or -24 VD C
(Refer to m anual)
BATTERY -
BATTERY +
INITIATING A1 -
INITIATING A2 -
INITIATING B1 +
INITIATING B2 +
S UPE RV ISOR Y HI
S UPE RV ISOR Y LO
TROUBLE RELAY NC
TROUBLE RELAY COM
TROUBLE RELAY NO
ALARM RELAY NC
ALARM RELAY COM
ALARM RELAY NO
Digital Alarm Communic ator Transmitter Listed for Ce ntral Station or Remote Station S ervice.
Slide Cover Back to A ccess Program ming Jack and Relays
Primary RJ31X
Te lco Ja ck
Alternate RJ31X
Te lco Ja ck
Phone Fa ult LED
- 12 VD C Sealed
Re ch argeabl e
+ B attery
+
-
NOTE on STD DACT:
Place jumper over pins 2 and 3,
marked DACT, when employing a
DACT. This directs the control panel
to transmit all trouble conditions
except AC LOSS.
STD DACT
To Central
Station
Alarm
JP-1
Motherboard 911AC
Alarm
normally open contacts
TB3-1 6 and 7
TB3-3 8 and 9
Trouble
normally open contacts
TB3-4 10
TB3-6 11
Supervisory
normally open contacts
4XZM TB1-12 12
jumper TB3-6 to
4XZM TB1-10
[DFFGU
To AC Power
36