NFPA Standard-Specific Requirements NFPA 72 Auxiliary Fire Alarm System
38 RP-1001 15150:F 05/24/2001
%1)3$$X[LOLDU\)LUH$ODUP6\VWHP
The Municipal Box circuit supervises for ground faults and opens (i.e. missing wire) but not for
direct short between two wires. It is not a power-limited circuit. This application is not suitable for
separate transmission of sprinkler supervisory or trouble conditions.
Note: Maximum loop resistance allowed for wiring from control panel to Municipal Box is 3 ohms.
;7%
FIRE
Gamewell
Model M34-56
Local Energy
Municipal Box
+
Municipal Box Circuit
-
4XTM
Transmitter Module
(activated polarities
shown)
+
-
6
7
$8;35266&'5