DANEO Control
53
COMTRADE and PCAP export
The instantaneous and binary signals of loaded recordings can be exported in COMTRADE 1999
format. You can also specify the signals to be exported, the sampling frequency, the COMTRADE
format, and the save path.
There is the possibility to directly open the exported file in an application associated to .cfg files, such
as the OMICRON application TransView. These applications are not included in DANEO Control and
have to be installed separately. For example, in case TransView is not found, the COMTRADE file is
exported correctly and an error message is displayed.
Recorded traffic can be exported by the captured ports (A, B, ETH) and is saved in PCAP format. One
file per selected port is generated.
Creating an analysis
You can create multiple time signal analysis and propagation delay views and therefore run multiple
analyses.
To create a new analysis, on the Event view, click Analysis, and then click Time Signal Analysis or
Propagation Delay.