RX Quick Start Guide 13
INSTALLATION
Power
Supply
P24 Internal 24 VDC Power supply for contact input signal 100 mA max
CM1
Input common Common terminal for P24, TH and FM digital monitor
Function Selection
FW Forward rotation command terminal Motor runs in forwards direction when FW is ON 27 VDC max
Input imped 4.7 k
Max current 5.6 mA
On: 18 VDC or more
1
Multi-function input Factory setting: Reverse (RV)
2
Factory setting: External trip (EXT)
3
Factory setting: Reset (RS)
4
Factory setting: Multi-step speed reference 1 (CF1)
5
Factory setting: Multi-step speed reference 2 (CF2)
6
Factory setting: Jogging (JG)
7
Factory setting: Second control (SET)
8
Factory setting: No allocation (NO)
PLC
Multi-function input common Sink logic: Short-circuiting P24 and PLC
Source logic: Short-circuiting PLC and CM1
With external supply remove short-circuit bar
Status/ Factor
11 Multi-function output Factory setting: During Run (RUN) 27 VDC max
50 mA max
12
Factory setting: 0 Hz signal (ZS)
13
Factory setting: Overload warning (OL)
14
Factory setting: Overtorque (OTQ)
15
Factory setting: Constant speed arrival (FA1)
CM2
Multi-function output common Common terminal for multi-function output terminals 11 to 15
Relay
output
AL1 Relay output (Normally close) Factory setting: Alarm output (AL)
Under normal operation
AL2-AL0 open
AL1-AL0 close
R load
AL1-AL0
250VAC 2A
AL2-AL0
250VAC 1A
I load
250 VAC 0.2 A
AL2
Relay output (Normally open)
AL0
Relay output common
Sensor
TH External thermistor input terminal SC terminal functions as the common terminal
100 mW minimum
Impedance at temperature error: 3 k
0 to 8 VDC
Comms
SP RS485 Modbus terminals - Differential input
SN
RP
RS485 terminating resistor terminals -- --
SN