RX Quick Start Guide 37
PARAMETER LIST
4.2 Parameter group A
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
Nº
Default
A001 Frequency reference selection 00: VR (Digital operator (FREQ adjuster))
01: Terminal
02: Digital operator (F001)
03: RS485 (Modbus communication)
04: Option 1
05: Option 2
06: Pulse train frequency
07: EzSQ (Drive programming)
10: (Math) Operation function result
– 1201h 01
A002 Run command selection 01: Terminal
02: Digital operator (F001)
03: RS485 (Modbus communication)
04: Option 1
05: Option2
– 1202h 01
A003 Base frequency 30 to maximum frequency [A004] Hz 1203h 50
A203 2nd set base frequency 30 to 2nd maximum frequency [A204] Hz
2203h 50
A303 3rd set base frequency 30 to 3rd maximum frequency [A304] Hz
3203h 50
A004 Maximum frequency A003 to 400 Hz 1204h 50
A204 2nd maximum frequency A203 to 400 Hz
2204h 50
A304 3rd maximum frequency A303 to 400 Hz
3204h 50
A005 O/OI selection 00: [O]/[OI] switches between O/OI terminal AT
01: [O]/[O2] switches between O/O2 terminal AT
02: [O]/VR switches between O/FREQ adjuster via ter-
minal AT (enabled only when 3G3AX-OP01 is used)
03: [OI]/VR switches between OI/FREQ adjuster via ter-
minal AT (enabled only when 3G3AX-OP01 is used)
04: [O2]/VR switches between O2/FREQ adjuster via ter-
minal AT (enabled only when 3G3AX-OP01 is used)
– 1205h 00
A006 O2 selection 00: [O2] only
01: [O/OI-P] auxiliary frequency reference (not revers-
ible)
02: [O/OI-PM] auxiliary frequency reference (reversible)
03: [OFF] O2 disabled
– 1206h 03
A011 O start frequency 0.00 to 400.00 Hz 120Bh 0.00
120Ch
A012 O end frequency 0.00 to 400.00 Hz 120Dh 0.00
120Eh
A013 O start ratio 0 to 100 % 120Fh 0
A014 O end ratio 0 to 100 % 1210h 100
A015 O start selection 00: External start frequency (A011 set value)
01: 0 Hz
– 1211h 01
A016 O, O2, OI sampling 1 to 30
31 (with 500 ms filter ±0.1 Hz hysteresis)
– 1212h 31
A017 Drive programming (EzSQ) selection 00: Disable
01: [PRG] start
02: Always ON
– 1213h 00
A019 Multi-step speed selection 00: Binary: 16-step selection with 4 terminals
01: Bit: 8-step selection with 7 terminals
– 1215h 00
A020 Multi-step speed reference 0 0.00 to max frequency [A004] Hz 1216h 6.00
1217h
A220 2nd multi-step speed reference 0 0.00 to max frequency [A204] Hz
2216h 6.00
2217h
A320 3rd multi-step speed reference 0 0.00 to max frequency [A304] Hz
3216h 6.00
3217h
A021 Multi-step speed reference 1 0.00/starting frequency to max frequency Hz 1218h 0.00
1219h
A022 Multi-step speed reference 2 0.00/starting frequency to max frequency Hz 121Ah 0.00
121Bh
A023 Multi-step speed reference 3 0.00/starting frequency to max frequency Hz 121Ch 0.00
121Dh
A024 Multi-step speed reference 4 0.00/starting frequency to max frequency Hz 121Eh 0.00
121Fh
A025 Multi-step speed reference 5 0.00/starting frequency to max frequency Hz 1220h 0.00
1221h
A026 Multi-step speed reference 6 0.00/starting frequency to max frequency Hz 1222h 0.00
1223h
A027 Multi-step speed reference 7 0.00/starting frequency to max frequency Hz 1224h 0.00
1225h
A028 Multi-step speed reference 8 0.00/starting frequency to max frequency Hz 1226h 0.00
1227h
A029 Multi-step speed reference 9 0.00/starting frequency to max frequency Hz 1228h 0.00
1229h
A030 Multi-step speed reference 10 0.00/starting frequency to max frequency Hz 122Ah 0.00
122Bh
A031 Multi-step speed reference 11 0.00/starting frequency to max frequency Hz 122Ch 0.00
122Dh