4.7 Parameter group F
4.8 Parameter group U: User parameters
Any function code can be register on these 32 parameters. When display mode is set be “user parameter” only U001 to U032 plus
d001, F001, b037 are displayed.
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default
F001 Output frequency setting/monitor
0.0/Starting frequency to 1st/2nd/3rd max. frequency
0.00 to 400.00
Hz
0001h
0.00
0002h
F002 Acceleration time 1 0.01 to 3600.00 s
1103h
10.00
1104h
F202 2nd acceleration time 1 0.01 to 3600.00 s
2103h
10.00
2104h
F302 3rd acceleration time 1 0.01 to 3600.00 s
3103h
10.00
3104h
F003 Deceleration time 1 0.01 to 3600.00 s
1105h
10.00
1106h
F203 2nd deceleration time 1 0.01 to 3600.00 s
2105h
10.00
2106h
F303 3rd deceleration time 1 0.01 to 3600.00 s
3105h
10.00
3106h
F004 Operator rotation direction selection 00: FWD (Forward)
01: REV (Reverse)
1107h 00
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default
U001 User 1 selection no/d001 to P196 - -no
U002 User 2 selection no/d001 to P196 - -no
U003 User 3 selection no/d001 to P196 - -no
U004 User 4 selection no/d001 to P196 - -no
U005 User 5 selection no/d001 to P196 - -no
U006 User 6 selection no/d001 to P196 - -no
U007 User 7 selection no/d001 to P196 - -no
U008 User 8 selection no/d001 to P196 - -no
U009 User 9 selection no/d001 to P196 - -no
U010 User 10 selection no/d001 to P196 - -no
U011 User 11 selection no/d001 to P196 - -no
U012 User 12 selection no/d001 to P196 - -no

Other manuals for Omron 3G3RX