RX Quick Start Guide 27
PROGRAMMING RX
All this functions could be assigned to any of the multi-function inputs on parameters C001 to C008, select if the input will be
normally open or normally close and the response time of the input.
An input terminal configured for option code 18 ([RS] Reset command) cannot be configured for normally closed operation.
3.14 Digital outputs
Function codes in the following table let you assign different options into logical outputs (terminals [11] to [15] and [AL]) on
parameter C021 to C026..
Parameter Parameter name Description
C001 Multi-function input 1 selection Select input terminal [1] function
C002 Multi-function input 2 selection Select input terminal [2] function
C003 Multi-function input 3 selection Select input terminal [3] function
C004 Multi-function input 4 selection Select input terminal [4] function
C005 Multi-function input 5 selection Select input terminal [5] function
C006 Multi-function input 6 selection Select input terminal [6] function
C007 Multi-function input 7 selection Select input terminal [7] function
C008 Multi-function input 8 selection Select input terminal [8] function
C011 Multi-function input 1 operation selection Select logic conversion:
00: NO (normally open)
01: NC (normally closed)
C012 Multi-function input 2 operation selection
C013 Multi-function input 3 operation selection
C014 Multi-function input 4 operation selection
C015 Multi-function input 5 operation selection
C016 Multi-function input 6 operation selection
C017 Multi-function input 7 operation selection
C018 Multi-function input 8 operation selection
C019 FW terminal operation selection
C160 Input terminal response time 1 Sets response time of each input terminal:
0 to 200 (x 2 ms)
C161 Input terminal response time 2
C162 Input terminal response time 3
C163 Input terminal response time 4
C164 Input terminal response time 5
C165 Input terminal response time 6
C166 Input terminal response time 7
C167 Input terminal response time 8
C168 FW terminal response time
d005 Multi-function input monitor
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description
00 RUN Run signal ON When the inverter is in Run Mode
01 FA1 Constant speed arrival signal ON When output to motor is at the set frequency
OFF When output to motor is OFF, or in any acceleration or deceleration ramp
02 FA2 Over set frequency arrival sig-
nal
ON When output to motor is at or above the set freq., even if in accel (C042) or decel
(C043) ramps
OFF When output to motor is OFF, or at a level below the set frequency
03 OL Overload warning ON When output current is more than the set threshold (C041) for the overload signal
04 OD Excessive PID deviation ON When PID error is more than the set threshold for the deviation signal
05 AL Alarm output ON When an alarm signal has occurred and has not been cleared
06 FA3 Set-frequency-only arrival sig-
nal
ON When output to motor is at the set frequency, during accel (C042) and decel (C043).
07 OTQ Overtorque ON Estimated motor torque exceeds the specified level
08 IP Signal during momentary
power interruption
ON Momentary power interruption/undervoltage
09 UV Signal during undervoltage ON Inverter is in undervoltage
10 TRQ Torque limit ON Torque limit function is executing
11 RNT RUN time over ON Total running time of the inverter exceeds the specified value
12 ONT Power ON time over ON Total power ON time of the inverter exceeds the specified value
13 THM Thermal warning ON Accumulated thermal count exceeds the C061 set value
19 BRK Brake release ON Output for brake release
MONITOR-A M1-STOP ALL
d005 Input
HLHLLLLHH
H001 00:OFF
1
2
3
4
5
6
7
8
FW
Example
FW, Multi-function input terminals 7, 2, 1: ON
Multi-function input terminals 8, 6, 5, 4, 3: OFF