RX Quick Start Guide
26 RX Quick Start Guide
32 SF1 Multi-step speed setting bit 1 ON Bit encoded speed select, Bit 1 to Bit 7
33 SF2 Multi-step speed setting bit 2
34 SF3 Multi-step speed setting bit 3
35 SF4 Multi-step speed setting bit 4 OFF
36 SF5 Multi-step speed setting bit 5
37 SF6 Multi-step speed setting bit 6
38 SF7 Multi-step speed setting bit 7
39 OLR Overload limit switching ON Perform overload restriction
OFF Normal operation
40 TL Torque limit enabled ON Setting of b040 is enabled
OFF Max. torque is limited with 200%
41 TRQ1 Torque limit switching 1 ON Torque limit related parameters of Powering/regen, and FW/RV modes are selected by the
combinations of these inputs.
42 TRQ2 Torque limit switching 2 OFF
43 PPI P/PI switching ON Proportional speed control for vector control
Off Proportional and integral speed control for vector control
44 BOK Brake confirmation ON Brake confirmation signal received
OFF Brake confirmation signal not received
45 ORT Orientation ON Orientation function is performed
46 LAC LAD cancel ON Set ramp times are ignored. Inverter output immediately follows the freq. command.
OFF Accel. and/or decel. is according to the set ramp time
47 PCLR Position deviation clear ON Clear the position deviation data
OFF Maintain the position deviation data
48 STAT Pulse train position command
input permission
ON Pulse train position command input enable
50 ADD Frequency addition ON Adds the A145 (add frequency) value to the output frequency
OFF Does not add the A145 value to the output frequency
51 F-TM Forced terminal block ON Force inverter to use input terminals for output frequency and Run command sources
OFF Source of output frequency set by A001 and source of Run command set by A002 is used
52 ATR Torque command input permis-
sion
ON Torque control command input is enabled
53 KHC Integrated power clearONClear watt-hour data
54 SON Servo ON ON Inverter enters in servo lock status
OFF Inverter goes into free-run status (Run command will not be accepted on this state)
55 FOC Preliminary excitation ON Supplies excitation current to the motor to establish magnetic flux
OFF Inverter goes into free-run status (Run command will not be accepted on this state)
56 MI1 Drive programming input 1 ON General purpose input (1) to (8) under Drive programming
57 MI2 Drive programming input 2
58 MI3 Drive programming input 3
59 MI4 Drive programming input 4
60 MI5 Drive programming input 5 OFF
61 MI6 Drive programming input 6
62 MI7 Drive programming input 7
63 MI8 Drive programming input 8
65 AHD Analog command held ON Analog command is held
OFF Analog command is not held
66 CP1 Position command selection 1 ON Multistage position commands are set according to the combination of these switches.
67 CP2 Position command selection 2 OFF
68 CP3 Position command selection 3
69 ORL Zero return limit signal ON Limit signal of homing is ON
70 ORG Zero return startup signal ON Starts homing operation
71 FOT Forward driving stop ON Torque limit is set to 10% on the forward direction
72 ROT Reverse driving stop ON Torque limit is set to 10% on the reverse direction
73 SPD Speed/position switching ON Speed control mode
OFF Position control mode
74 PCNT Pulse counter - Input works as a counter which value could be check in monitor d028.
75 PCC Pulse counter clear ON Clears the total count value (d028)
82 PRG Drive program start ON Executing Drive program
OFF No execution
255 no No allocation - (input ignored)
Input Function Summary Table