RX Quick Start Guide 17
PROGRAMMING RX
3.6 Basic settings
After selecting the inverter mode follow next steps for a basic operation of the inverter
Select frequency reference source on parameter A001
Select Run command source on parameter A002
Adjust the stopping method by b091 and the acceleration/deceleration ramps on parameters F002 and F003
Set the motor base frequency and AVR voltage of the motors in parameters A003 and A082
Set the motor data: rated current (b012), rated power (H003) and number of poles (H004)
When working in sensorless vector control, 0-Hz sensorless vector or sensor vector control always perform motor auto tun-
ing by parameter H001 to achieve a good performance (see next section for details)
At this point the inverter is ready to run the motor for the first time, but first review this check-list:
Verify the power LED is ON. If not, check the power connections.
Make sure the motor is disconnected from any mechanical load.
Make sure that you have a frequency reference checking the content of F001
Now give the RUN command from the selected source. The RUN LED will turn ON.
The motor should start turning.
Remove the RUN command or press the STOP key to stop the motor rotation.
Carrier frequency b083 0.5 to 15.0(kHz) 0.4-55kW
0.5 to 10.0(kHz) 75-132kW
5.0(kHz) 0.4-55kW 0.5 to 10.0(kHz) 0.4-55kW
0.5 to 8.0(kHz) 75 - 132kW
3.0(kHz)
Motor capacity selection H003 0.2 to 160(kW) Depends on type 0.4 to 160(kW) 1 size up than HD
Parameter Parameter Name Details
A001 Frequency reference selection 00: VR (Digital Operator (FREQ adjuster)
01: Terminal
02: Digital operator (F001)
03: RS485 (ModBus communication)
04: Option 1
05: Option 2
06: Pulse train frequency
07: EzSQ (Drive programming)
10: (Math) Operation function result
Parameter Parameter Name Details
A002 Run command selection 01: Terminal
02: Digital Operator (F001)
03: RS485 (ModBus communication)
04: Option 1
05: Option 2
Parameter Parameter Name Details
b091 Stop selection 00: Decel-Stop (Deceleration to stop)
01: Free-RUN (Free run stop)
F002 Acceleration time 1 0.01 to 3600.00
F003 Deceleration time 1 0.01 to 3600.00
Parameter Parameter Name Details
A003 Base frequency 30.0 to maximum frequency [A004]
A082 AVR voltage selection 200-V class: 200 to 240V
400-V class: 380 to 480V
Parameter Parameter Name Details
b012 Electronic thermal level 0.20 x Rated current to 1.00 x Rated current
H003 Motor capacity selection 0.20 to 160.0 kW
H004 Motor pole number selection 2 to 10 poles
P011 Encoder pulses 128 to 65535 (Only for sensor vector control)