4.3 Parameter group B
A105 OI start selection 00: Start FQ (Use OI start frequency [A101])
01: 0 Hz
1287h 00
A111 O2 start frequency -400.00 to 400.00 Hz
128Dh 0.00
128Eh
A112 O2 end frequency -400.00 to 400.00 Hz
128Fh 0.00
1290h
A113 O2 start ratio -100 to O2 end ratio %
1291h -100
A114 O2 end ratio O2 start ratio to 100 %
1292h 100
A131 Acceleration curve parameter 01 (small curve) to 10 (large curve) 12A5h 02
A132 Deceleration curve parameter 01 (small curve) to 10 (large curve) - 12A6h 02
A141 Operation frequency input A setting 00: Operator (Digital operator (F001))
01: VR (Digital operator (FREQ adjuster)) (Enabled
when 3G3AX-OP01 is used)
02: O (Input O)
03: OI (Input OI)
04: Modbus (RS485 communication)
05: Option 1
06: Option 2
07: Pulse (Pulse train frequency)
- 12AFh 02
A142 Operation frequency input B setting 00: Operator (Digital operator (F001))
01: VR (Digital operator (FREQ adjuster)) (Enabled
when 3G3AX-OP01 is used)
02: O (Input O)
03: OI (Input OI)
04: Modbus (RS485 communication)
05: Option 1
06: Option 2
07: Pulse (Pulse train frequency)
12B0h 03
A143 Operator selection 00: ADD (Addition (A + B))
01: SUB (Substraction (A - B))
03: MUL (Multiplication (A x B))
12B1h 00
A145 Frequency addition amount 0.00 to 400.00 Hz 12B3h 0.00
12B4h
A146 Frequency addition direction 00: ADD (Add A145 value to output frequency)
01: SUB (Subtract A145 value from output frequency)
12B5h 00
A150 EL-S-curve ratio 1 during acceleration 0 to 50 % 12B9h 10
A151 EL-S-curve ratio 2 during acceleration 0 to 50 % 12BAh 10
A152 EL-S-curve ratio 1 during deceleration 0 to 50 % 12BBh 10
A153 EL-S-curve ratio 2 during deceleration 0 to 50 % 12BCh 10
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default
b001 Retry selection 00: TRIP (Alarm)
01: 0 Hz start
02: f-match (Frequency matching start)
03: f-match trip (Trip after frequency matching decelera-
tion stop)
04: Actv. f-match (Active frequency matching restart)
1301h 00
b002 Allowable momentary power interruption time 0.3 to 25.0 s 1302h 1.0
b003 Retry wait time 0.3 to 100.0 s 1303h 1.0
b004 Momentary power interruption/undervoltage trip
during stop selection
00: OFF (Disabled)
01: ON (Enabled)
02: Decel-OFF (Disabled during stop and deceleration
stop)
1304h 00
b005 Momentary power interruption retry time selection 00: 16 times
01: No limit
1305h 00
b006 Input phase loss protection selection 00: OFF (Disabled)
01: ON (Enabled)
1306h 00
b007 Frequency matching lower limit frequency setting 0.00 to 400.00 Hz 1307h 0.00
1308h
b008 Trip retry selection 00: TRIP (Alarm)
01: 0 Hz start
02: f-match (Frequency matching start)
03: f-match trip (Trip after frequency matching decelera-
tion stop)
04: Actv. f-match (Active frequency matching restart)
1309h 00
b009 Undervoltage retry time selection 00: 16 times
01: No limit
130Ah 00
b010 Overvoltage/overcurrent retry time selection 1 to 3 Time 130Bh 3
b011 Trip retry wait time 0.3 to 100.0 s 130Ch 1.0
b012 Electronic thermal level 0.20 x Rated current to 1.00 x Rated current A 130Dh -
b212 2nd electronic thermal level 0.20 x Rated current to 1.00 x Rated current A 230Ch -
b312 3rd electronic thermal level 0.20 x Rated current to 1.00 x Rated current A 330Ch -
b013 Electronic thermal characteristics selection 00: Reduced TRQ (Reduced torque characteristics)
01: Const TRQ (Constant torque characteristics)
02: Free set (Free setting)
130Eh 00
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
Default