RX Quick Start Guide 41
PARAMETER LIST
b213 2nd electronic thermal characteristics selection 00: Reduced TRQ (Reduced torque characteristics)
01: Const TRQ (Constant torque characteristics)
02: Free set (Free setting)
230Dh 00
b313 3rd electronic thermal characteristics selection 00: Reduced TRQ (Reduced torque characteristics)
01: Const TRQ (Constant torque characteristics)
02: Free set (Free setting)
330Dh 00
b015 Free setting, electronic thermal frequency 1 0.00 to 400.00 Hz 1310h 0.00
b016 Free setting, electronic thermal current 1 0.0 to Rated current A 1311h 0.00
b017 Free setting, electronic thermal frequency 2 0.00 to 400.00 Hz 1312h 0.00
b018 Free setting, electronic thermal current 2 0.0 to Rated current A 1313h 0.00
b019 Free setting, electronic thermal frequency 3 0.00 to 400.00 Hz 1314h 0.00
b020 Free setting, electronic thermal current 3 0.0 to Rated current A 1315h 0.00
b021 Overload limit selection 00: OFF (Disabled)
01: ON-Acc/Cnst (Enabled in acceleration/constant
speed operation)
02: ON-Cnst (Enabled in constant speed operation)
03: ON-A/C(R) (Enabled in acceleration/constant speed
operation (Accelerates during regeneration))
1316h 01
b022 Overload limit level 0.20 x Rat current to 2.00 x Rat current (0.4 to 55 kW)
0.20 x Rat current to 1.80 x Rat current (75 to 132 kW)
A 1317h -
b023 Overload limit parameter 0.10 to 30.00 s 1318h 1.00
b024 Overload limit selection 2 00: OFF (Disabled)
01: ON-Acc/Cnst (Enabled in acceleration/constant
speed operation)
02: ON-Cnst (Enabled in constant speed operation)
03: ON-A/C(R) (Enabled in acceleration/constant speed
operation (Accelerates during regeneration))
1319h 01
b025 Overload limit level 2 0.20 x Rat current to 2.00 x Rat current (0.4 to 55 kW)
0.20 x Rat current to 1.80 x Rat current (75 to 132 kW)
A 131Ah -
b026 Overload limit parameter 2 0.10 to 30.00 s 131Bh 1.00
b027 Overcurrent suppression function 00: OFF (Disabled)
01: ON (Enabled)
131Ch 00
b028 Active frequency matching restart level 0.20 x Rat current to 2.00 x Rat current (0.4 to 55 kW)
0.20 x Rat current to 1.80 x Rat current (75 to 132 kW)
A 131Dh -
b029 Active frequency matching restart parameter 0.10 to 30.00 s 131Eh 0.50
b030 Starting frequency at active frequency matching
restart
00: Off FQ (Frequency at interruption)
01: Max.FQ (Max. frequency)
02: Set FQ (Set frequency)
131Fh 00
b031 Soft lock selection 00: Lock (SFT) (Data other than b031 cannot be changed
when terminal SFT is ON)
01: Only FQ (SFT) (Data other than b031 and the speci-
fied frequency parameter cannot be changed when ter-
minal SFT is ON)
02: Lock (Data other than b031 cannot be changed)
03: Only FQ (Data other than b031 and the specified fre-
quency parameter cannot be changed)
10: RUN chg mode (Data other than parameters change-
able during operation cannot be changed)
1320h 01
b034 RUN time/Power ON time setting 0 to 65535 h 1323h 0
1324h
b035 Rotation direction limit selection 00: FREE (Forward and reverse are enabled)
01: FWD (Only forward is enabled)
02: REV (Only reverse is enabled)
1325h 00
b036 Reduced voltage startup selection 0 (reduced voltage startup time: small) to 255 (reduced
voltage startup time: large)
1326h 6
b037 Display selection 00: All (Complete display)
01: Utilized (Individual display of functions)
02: User (User setting)
03: Compare (Data comparison display)
04: Basic (Basic display)
1327h 00
b038 Initial screen selection 000 to 202 1328h 001
b039 User parameter automatic setting function selection 00: OFF (Disabled)
01: ON (Enabled)
1329h 00
b040 Torque limit selection 00: 4-quadrant (Four-quadrant separate setting)
01: TRQ input (Terminal switch)
02: [O] input (Analogue input)
03: Option 1
04: Option 2
132Ah 00
b041 Torque limit 1
(fwd-power in 4-quadrant mode)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
% 132Bh 150
b042 Torque limit 2
(rev/regen. in 4-quadrant mode)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
% 132Ch 150
b043 Torque limit 3
(rev/power in 4-quadrant mode)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
% 132Dh 150
b044 Torque limit 4
(fwd/regen. in 4-quadrant mode)
0 to 200 (0.4 to 55 kW)
0 to 180 (75 to 132 kW)
no (Torque limit disabled)
% 132Eh 150
b045 Torque LADSTOP selection 00: OFF (Disabled)
01: ON (Enabled)
132Fh 00
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default