RX Quick Start Guide 43
PARAMETER LIST
4.4 Parameter group C
b110 Free V/F frequency 6 0 to free V/F frequency 7 Hz 1371h 0
b111 Free V/F voltage 6 0.0 to 800.0 V 1372h 0.0
b112 Free V/F frequency 7 0 to 400 Hz 1373h 0
b113 Free V/F voltage 7 0.0 to 800.0 V 1374h 0.0
b120 Brake control selection 00: OFF (Disabled)
01: ON (Enabled)
– 137Bh 00
b121 Brake wait time for release 0.00 to 5.00 s 137Ch 0.00
b122 Brake wait time for acceleration 0.00 to 5.00 s 137Dh 0.00
b123 Brake wait time for stopping 0.00 to 5.00 s 137Eh 0.00
b124 Brake wait time for confirmation 0.00 to 5.00 s 137Fh 0.00
b125 Brake release frequency 0.00 to -400.00 Hz 1380h 0.00
b126 Brake release current 0.0 to 2.00 x Rated current (0.4 to 55 kW)
0.0 to 1.80 x Rated current (75 to 132 kW)
– 1381h -
b127 Brake input frequency 0.00 to 400.00 Hz 1382h 0.00
b130 Overvoltage protection function selection during
deceleration
00: OFF (Disabled)
01: V-const (DC voltage kept constant)
02: Accel (Acceleration enabled)
– 1385h 01
b131 Overvoltage protection level during deceleration 200-V class: 330 to 390
400-V class: 660 to 780
V 1386h 380/760
b132 Overvoltage protection parameter 0.10 to 30.00 s 1387h 1.00
b133 Overvoltage protection proportional gain 0.00 to 2.55 – 1388h 0.50
b134 Overvoltage protection integral time setting 0.000 to 65.535 s 1389h 0.060
b164 Auto return initial display 00: OFF
01: ON
– 13A7h 00
b166 Data read/write selection 00: R/W OK (Read/Write OK)
01: R/W protected (Read/Write protected)
– 13A9h 00
b180 Initialize trigger 00: No action
01: Initialize
– 13B7h 00
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default
C001 Multi-function input 1 selection Check Digital inputs on page 23 – 1401h 01
C002 Multi-function input 2 selection – 1402h 12
C003 Multi-function input 3 selection – 1403h 18
C004 Multi-function input 4 selection – 1404h 02
C005 Multi-function input 5 selection – 1405h 03
C006 Multi-function input 6 selection – 1406h 06
C007 Multi-function input 7 selection – 1407h 08
C008 Multi-function input 8 selection – 1408h no
C011 Multi-function input 1 operation selection 00: NO
01: NC
– 140Bh 00
C012 Multi-function input 2 operation selection 00: NO
01: NC
– 140Ch 00
C013 Multi-function input 3 operation selection 00: NO
01: NC
– 140Dh 00
C014 Multi-function input 4 operation selection 00: NO
01: NC
– 140Eh 00
C015 Multi-function input 5 operation selection 00: NO
01: NC
– 140Fh 00
C016 Multi-function input 6 operation selection 00: NO
01: NC
– 1410h 00
C017 Multi-function input 7 operation selection 00: NO
01: NC
– 1411h 00
C018 Multi-function input 8 operation selection 00: NO
01: NC
– 1412h 00
C019 FW terminal operation selection 00: NO
01: NC
– 1413h 00
C021 Multi-function output terminal 11 selection Check Digital inputs on page 25 – 1415h 00
C022 Multi-function output terminal 12 selection – 1416h 21
C023 Multi-function output terminal 13 selection – 1417h 03
C024 Multi-function output terminal 14 selection – 1418h 07
C025 Multi-function output terminal 15 selection – 1419h 01
C026 Relay output (AL2, AL1) function selection – 141Ah 05
C027 FM selection Check Analogue outputs on page 27 – 141Bh 00
C028 AM selection Check Analogue outputs on page 27 – 141Ch 00
C029 AMI selection Check Analogue outputs on page 27 – 141Dh 00
C030 Digital current monitor reference value 0.20 x Rated current to 2.00 x Rated current – 141Eh -
C031 Multi-function output terminal 11 contact selection 00: NO
01: NC
– 141Fh 00
C032 Multi-function output terminal 12 contact selection 00: NO
01: NC
– 1420h 00
C033 Multi-function output terminal 13 contact selection 00: NO
01: NC
– 1421h 00
C034 Multi-function output terminal 14 contact selection 00: NO
01: NC
– 1422h 00
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default