RX Quick Start Guide
28 RX Quick Start Guide
In the same way of that the digital inputs is possible to choose between normally close and normally open and even is possible to
use some On and Off delay for each of the outputs.
20 BER Brake error ON Brake error has occurred
21 ZS 0 Hz signal ON Output frequency falls below the threshold specified in C063
22 DSE Excessive speed deviation ON Deviation of speed command and actual speed exceeds the specified value P027.
23 POK Position ready ON Positioning is completed
24 FA4 Set frequency exceeded 2 ON When output to motor is at or above the set freq., even if in accel (C045) or decel
(C046) ramps
25 FA5 Set frequency only 2 ON When output to motor is at the set frequency, during accel (C045) and decel (C046).
26 OL2 Overload warning 2 ON When output current is more than the set threshold (C111) for the overload signal
27 ODc Analog O disconnection detec-
tion
ON When the [O] input value < B070 setting (signal loss detected)
28 OIDc Analog OI disconnection
detection
ON When the [OI] input value < B071 setting (signal loss detected)
29 O2Dc Analog O2 disconnection
detection
ON When the [O2] input value < B072 setting (signal loss detected)
31 FBV PID FB status output ON Transitions to ON when the inverter is in RUN Mode and the PID Process Variable
(PV) is less than the Feedback Low Limit (C053)
OFF Transitions to OFF when the PID Process Variable (PV) exceeds the PID High Limit
(C052), and transitions to OFF when the inverter goes from Run Mode to Stop Mode
32 NDc Network error ON When communications watchdog timer (period specified by C077) has time out
33 LOG1 Logic operation output 1 ON When the Boolean operation specified by C144 has a logical “1” result
34 LOG2 Logic operation output 2 ON When the Boolean operation specified by C147 has a logical “1” result
35 LOG3 Logic operation output 3 ON When the Boolean operation specified by C150 has a logical “1” result
36 LOG4 Logic operation output 4 ON When the Boolean operation specified by C153 has a logical “1” result
37 LOG5 Logic operation output 5 ON When the Boolean operation specified by C156 has a logical “1” result
38 LOG6 Logic operation output 6 ON When the Boolean operation specified by C159 has a logical “1” result
39 WAC Capacitor life warning signal ON Lifetime of internal capacitor has expired.
40 WAF Cooling fan life warning signal ON Lifetime of cooling fan has expired.
41 FR Starting contact signal ON Either FW or RV command is given to the inverter
OFF No FW or RV command is given to the inverter, or both are given to the inverter
42 OHF Fin overheat warning ON Temperature of the heat sink exceeds a specified value (C064)
43 LOC Light load detection signal ON Motor current is less than the specified value (C039)
44 MO1 Drive programming output 1 ON General output 1 is ON (Used by Drive programing)
45 MO2 Drive programming output 2 ON General output 2 is ON (Used by Drive programing)
46 MO3 Drive programming output 3 ON General output 3 is ON (Used by Drive programing)
47 MO4 Drive programming output 4 ON General output 4 is ON (Used by Drive programing)
48 MO5 Drive programming output 5 ON General output 5 is ON (Used by Drive programing)
49 MO6 Drive programming output 6 ON General output 6 is ON (Used by Drive programing)
50 IRDY Operation ready signal ON Inverter can receive a run command
51 FWR Forward run signal ON Inverter is driving the motor in forward direction
52 RVR Reverse run signal ON Inverter is driving the motor in reverse direction
53 MJA Fatal fault signal ON Inverter is tripping with major failure
54 WCO Window comparator O ON Analog voltage input value is inside of the window comparator (b060 to b062)
55 WCOI Window comparator OI ON Analog current input value is inside of the window comparator (b063 to b065)
56 WCO2 Window comparator O2 ON Analog voltage input value is inside of the window comparator (b066 to b068)
63 OPO Option board output ON (output terminal for option card)
255 no Not used ON
Parameter Parameter name Description
C021 Multi-function output terminal 11 selection Programmable functions available for logic
(discrete) outputs transistor type
C022 Multi-function output terminal 12 selection
C023 Multi-function output terminal 13 selection
C024 Multi-function output terminal 14 selection
C025 Multi-function output terminal 15 selection
C026 Relay output (AL2, AL1) function selection Programmable functions available for logic
(discrete) outputs relay type
C031 Multi-function output terminal 11 contact selection Select logic conversion:
00: NO contact at AL2; NC contact at AL1
01: NC contact at AL2; NO contact at AL1
C032 Multi-function output terminal 12 contact selection
C033 Multi-function output terminal 13 contact selection
C034 Multi-function output terminal 14 contact selection
C035 Multi-function output terminal 15 contact selection
C036 Relay output (AL2, AL1) contact selection
Output Function Summary Table
Option
Code
Terminal
Symbol
Function Name Description