RX Quick Start Guide 45
PARAMETER LIST
C103 Reset frequency matching selection 00: 0 Hz start
01: f-match (Frequency matching start)
02: Actv. f-match (Active frequency matching restart)
– 146Bh 00
C105 FM gain setting 50 to 200 % 146Dh 100
C106 AM gain setting 50 to 200 % 146Eh 100
C107 AMI gain setting 50 to 200 % 146Fh 100
C109 AM bias setting 0 to 100 % 1471h 0
C110 AMI bias setting 0 to 100 % 1472h 20
C111 Overload warning level 2 0.0 to 2.00 x Rated current (0.4 to 55 kW)
0.0 to 1.80 x Rated current (75 to 132 kW)
A 1473h -
C121 O zero adjustment 0 to 65535 – 147Dh Factory
default
C122 OI zero adjustment 0 to 65535 – 147Eh Factory
default
C123 O2 zero adjustment 0 to 65535 – 147Fh Factory
default
C130 Output 11 ON delay 0.0 to 100.0 s 1486h 0.0
C131 Output 11 OFF delay 0.0 to 100.0 s 1487h 0.0
C132 Output 12 ON delay 0.0 to 100.0 s 1488h 0.0
C133 Output 12 OFF delay 0.0 to 100.0 s 1489h 0.0
C134 Output 13 ON delay 0.0 to 100.0 s 148Ah 0.0
C135 Output 13 OFF delay 0.0 to 100.0 s 148Bh 0.0
C136 Output 14 ON delay 0.0 to 100.0 s 148Ch 0.0
C137 Output 14 OFF delay 0.0 to 100.0 s 148Dh 0.0
C138 Output 15 ON delay 0.0 to 100.0 s 148Eh 0.0
C139 Output 15 OFF delay 0.0 to 100.0 s 148Fh 0.0
C140 Relay output ON delay 0.0 to 100.0 s 1490h 0.0
C141 Relay output OFF delay 0.0 to 100.0 s 1491h 0.0
C142 Logic output signal 1 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1492h 00
C143 Logic output signal 1 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1493h 00
C144 Logic output signal 1 operator selection 00: AND
01: OR
02: XOR
– 1494h 00
C145 Logic output signal 2 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1495h 00
C146 Logic output signal 2 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1496h 00
C147 Logical output signal 2 operator selection 00: AND
01: OR
02: XOR
– 1497h 00
C148 Logic output signal 3 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1498h 00
C149 Logic output signal 3 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 1499h 00
C150 Logical output signal 3 operator selection 00: AND
01: OR
02: XOR
– 149Ah 00
C151 Logic output signal 4 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 149Bh 00
C152 Logic output signal 4 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 149Ch 00
C153 Logical output signal 4 operator selection 00: AND
01: OR
02: XOR
– 149Dh 00
C154 Logic output signal 5 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 149Eh 00
C155 Logic output signal 5 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 149Fh 00
C156 Logical output signal 5 operator selection 00: AND
01: OR
02: XOR
– 14A0h 00
C157 Logic output signal 6 selection 1 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 14A1h 00
C158 Logic output signal 6 selection 2 Same as options for C021 to C026
(excluding LOG1 to LOG6)
– 14A2h 00
C159 Logical output signal 6 operator selection 00: AND
01: OR
02: XOR
– 14A3h 00
C160 Input terminal response time 1 0 to 200 (x 2 ms) ms 14A4h 1
C161 Input terminal response time 2 0 to 200 (x 2 ms) ms 14A5h 1
C162 Input terminal response time 3 0 to 200 (x 2 ms) ms 14A6h 1
C163 Input terminal response time 4 0 to 200 (x 2 ms) ms 14A7h 1
Function code Function name Monitoring and setting items Units Run
mode
edit
Modbus
Register
No.
Default