3 Checking and starting the operation
3-4 Operations using the LCD menu
BU5002R/BU3002R/BU3002RH
90
: Displayed only when the UPS is stopped. Not displayed while the UPS is running.
Menu
Description
Value
Menu type
Settings
Dry Contact
BSsignal Delay
Time
Sets the delay time for a BS
signal.
BS signal delay time:
0 to 9000 seconds, or
9999 seconds (factory default: 0
seconds)
(Note 5)
Advanced
BUsignal Delay
Time
Sets the delay time for a BU
signal.
BU signal delay time:
0 to 900 milliseconds, or
0 to 180 seconds (factory default: 0
seconds)
(Note 3)
Dry Contact
Logic
Sets the dry contact logic.
Dry Contact logic:
BU, BL, TR, WB:
Normal (factory default)/
Reverse
Remote
ON/OFF Logic
Sets the remote signal logic.
Remote ON/OFF logic:
OFF when short-circuited (factory
default),
OFF when opened, Disabled
Identific
ation
Type
Displays the names of the
UPS and battery pack.
Type name:
UPS: Model,
Battery: Model
Standard
Serial Number
Displays the serial number of
the UPS.
Serial number:
S/N:xxxxxxxxxxxxxxxG
Firmware Version
Displays the firmware
version of the UPS.
Firmware version:
UPS:M:x.xx
USB : S:-.--
(The UPS does not support USB)
Advanced
Memorandum
Information up to 20
alphanumeric characters can
be viewed.
-
Log
Fault Log
Displays up to 10 logs of
faults that occurred in the
past (time of occurrence and
fault details).
Fault log:
Year/month/day/hour/minute,
message
Advanced
Shutdown Log
Display up to 10 reasons for
UPS shutdown.
Shutdown log:
Year/month/day/hour/minute,
message
AC input Log
Displays up to 10 logs of
events that occurred in the
past.
AC input log:
Year/month/day/hour/minute,
message
Reset All Log Data
Clears each piece of log
data.
Executes Reset All Log Data