268
Advanced Function Setting Level Section 5-10
• This parameter specifies the operation for when the mode is changed
from Remote SP Mode to Local SP Mode.
• When this parameter is set to ON, Local SP Mode inherits the remote SP.
• When this parameter is set to OFF, the local SP is not affected by the
remote SP.
â– Related Parameters
Set point during SP ramp (operation level): Page 180
SP mode (adjustment level): Page 193
• When this parameter is set to ON, the output to which alarm 1 is assigned
turns ON when a remote SP input error occurs.
Note For details on input errors, refer to 4-23 Using a Remote SP Func-
tion.
• The output is an OR output between alarm 1, the heater burnout/HS/
heater overcurrent alarm, the input error, and the RSP input error status.
• The output turns OFF when switching to the initial setting level, advanced
function setting level, communications setting level, or calibration level.
â– Related Parameters
Remote SP upper limit, Remote SP lower limit (advanced function setting
level): Page 267
SP mode (adjustment level): Page 193
sptr SP Tracking
The ST parameter must be set to
OFF.
The Remote SP Enable parameter
must be set to OFF.
Setting range Default
ON: Enabled, OFF: Disabled off
Function
Setting
See
See
rseo
Remote SP Input
Error Output
The ST parameter must be set to
OFF.
The Remote SP Enable parameter
must be set to ON.
Alarm 1 must be assigned, but not to
a work bit output.
Setting range Default
ON: Enabled, OFF: Disabled off
Function
Setting
See
See