580
Commands/Responses
Section 9-3
Response
Only if ”Yes” is set for the ”Response” memory switch, the response indicated be-
low is returned on normal completion.
[Format]
1B 57
[
ESC
]
[CR
]
W
3030 32 0D4E
N
30
0 0 s1 s2
s
1
,s
2
: Check sum (2 hexadecimal digits)
This is always added (fixed as “20H”).
[Function]
S Writes the data of the specified number of numeral memory tables, starting from
the specified numeral memory tables.
S A maximum of 20 tables can be written at one time.
S When writing is executed to numeral memory tables from No.247 to No.253
(areas for clock data display/reading useonly), operation will be finished normal-
ly without writing values.
Reference:
S Data written by a numeral memory table write command is written according to
the numeral storage type of the numeral. Numeral storage type can be set at the
Support Tool. (It is possible to set it by a system memory at a PT collectively.)
e.g.) Writing 1234 to the numeral memory table No.0 (allocated word: 1)
Written data Numeral Strage Type
Numeral Memory Table No. 0
Binary
BCD
1234
04D2
1234
S For details of function and setting of numeral storage type, refer to ”NT-series
Support Tool for Windows 95/98 (Ver.3.0) Operation Manual” (V053--E1).