5 - 35
5   I/O Refreshing
NX-series Digital I/O Unit User’s Manual (W521)
5-2  I/O Refreshing Methods
5
5-2-10  An Example of Turning ON Outputs at Specific Times After the Sensor Inputs Change
The following I/O map settings are used.
However, add 0x200A: 02 (Time Stamp of Synchronous Output) to an I/O entry mapping of the Ether-
CAT Coupler Unit.
I/O Map
Position Port Description R/W
Data 
type
Variable
Variable 
type
Node1 Time Stamp of 
Synchronous 
Output
Contains the time stamp 
for the timing of 
synchronous outputs from 
the connected NX Unit. 
(Unit: ns)
R ULINT E001_Time_Stamp_
of_Synchronous_Ou
tput
Global 
variable
Unit1 Input Bit 00 
Time Stamp
Input changed time for 
input bit 00
R ULINT N1_Input_Bit_00_Ti
me_Stamp
Global 
variable
Unit2 Output Bit 00 
Time Stamp
Specified time for output bit 
00
W ULINT N2_Output_Bit_00_
Time_Stamp
Global 
variable
Unit2 Output Bit 00 Output bit 00 W BOOL N2_Output_Bit_00 Global 
variable
Unit2 Output Bit 00 
Output Status
Output status 00 R BOOL N2_Output_Bit_00_
Output_Status
Global 
variable