4 - 39
4 Installation and Wiring
NX-series Digital I/O Unit Users Manual (W521)
4-3 Wiring the Terminals
4
4-3-4 Checking the Wiring
Check the wiring by reading input data or writing output data from Slave Terminals using the Watch Tab
Page of the Support Software.
For Input Units, you can turn ON/OFF the inputs from external devices that are connected to the target
Units and monitor the results.
For Output Units, you can execute the I/O outputs of the target Units and check the operation of the
connected external devices.
For details on monitoring and I/O output operations using the Support Software, refer to the operation
manual for the Support Software that you are using.
Additional Information
If you check the wiring for the Output Units that support output refreshing with specified time
stamp, set the value of the Output Bit  Time Stamp parameter to 0. At this time, the Out-
put Units refresh outputs immediately and outputs are refreshed according to the output set
values.
In the Sysmac Studio, you can check the wiring from the I/O Map or Watch Tab Page. If you
use the I/O Map, you can also monitor and perform forced refreshing even if the variables are
not defined or the algorithms are not created. Therefore, you can easily check the wiring.
Refer to the Sysmac Studio Version 1 Operation Manual (Cat. No. W504) for details on mon-
itoring and forced refreshing operations.
Some Communications Coupler Units support I/O checking that allows you to check wiring
with only the Slave Terminal. Refer to the user's manual of the Communications Coupler Unit
for detailed information on the support and functionality of I/O checking for your Communica-
tions Coupler Unit.