5 - 53
5 Installation and Wiring
NX-series NX1P2 CPU Unit Hardware Users Manual (W578)
5-4 Wiring
5
5-4-8 Wiring to the CPU Unit Terminal Block
Secure wires within the range of 30 mm from the screwless clamping terminal block.
Also, leave spaces above and below the CPU Rack to ensure ventilation, as shown in the
following figure.
Removing Wires
Use the following procedure to remove the wires from the terminal block.
The removal method is the same for ferrules, twisted wires, and solid wires.
If wires are secured firmly to the terminal block, release them first.
1 Press the a flat-blade screwdriver straight into the release hole.
If you press in the screwdriver correctly, you will feel the spring in the release hole, and the
screw driver will begin to incline.
2 Leave the flat-blade screwdriver pressed into the release hole and pull out the wire.
Wiring duct
Spaces to
ensure
ventilation
Wiring duct
30 mm
1
Wire
Flat-blade screwdriver
2