0
Function See
page
User
set
values
Initial
setting
DescriptionNameNo.
7 Minimum
output fre-
quency
Setting unit: 0.1 Hz, setting range; 0.1 to
10 Hz
1.5 Hz 44
8 Minimum
output fre-
quency volt-
age
Setting unit: 0.1 V, setting range: 0.1 to 50 V 12.0 V 44
First ac-
cel/decel
9 Acceleration
time 1
Setting unit: 0.1 s, setting range: 0.0 to
600.0 s
10.0 s 46
time set-
ting
10 Deceleration
time 1
Setting unit: 0.1 s, setting range: 0.0 to
600.0 s
10.0 s 46
Second
accel/de-
11 Acceleration
time 2
Setting unit: 0.1 s, setting range: 0.0 to
600.0 s
10.0 s 46
cel time
setting
12 Deceleration
time 2
Setting unit: 0.1 s, setting range: 0.0 to
600.0 s
10.0 s 46
Frequen-
cy refer-
13 Frequency
reference 1
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz 45
ence (see
note 1)
14 Frequency
reference 2
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz 45
15 Frequency
reference 3
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz 45
16 Frequency
reference 4
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
0.0 Hz 45
17 Jogging fre-
quency ref-
erence
Setting unit: 0.1 Hz, setting range: 0.0 to
400.0 Hz
6.0 Hz 45
Electronic
thermal
overload
motor pro-
tection
18 Motor pro-
tection se-
lection
1st digit = 0: Electronic thermal overload
motor protection provided
1: Electronic thermal overload
motor protection not provided
2nd digit = 0: Electronic thermal overload
characteristic is for standard
motor
1: Electronic thermal overload
characteristic is for constant
torque motor
3rd digit Not used
4th digit: Not used
0000 47
Electronic
thermal
overload
reference
current
19 Motor rated
current
Setting unit: 0.1 A, setting range: 10% to
120% of inverter rated current
1.9 A (see
note 2)
47
Note 1. Can be changed even during run.
2. Initial setting differs according to the inverter capacity. the val-
ues in the above list are provided when model 3G3SV-B2004
(0.4 kW) and standard motor 200 V 60 Hz. 0.4 kW are com-
bined. Set the values described in the motor nameplate.
"
Section 2-9