2 Instructions
2-224
CP1E CPU Unit Instructions Reference Manual(W483)
This example shows how to construct a linear extrapolation with 12 coordinates. The block of data is
continuous, as it must be, from D0 to D26 (C to C + (2 × 12 + 2)). The input data is taken from CIO 10,
and the result is output to CIO 11.
In this case, the source word, CIO 0010, contains 0014, and f(0014) = 0726 is output to R, CIO 0011.
The linear-extrapolation calculation is shown below.
• Y
n
= f(X
n
), Y
0
= f(X
0
)
• Be sure that X
n-1
< X
n
in all cases.
• Input all values of (X
n
, Y
n
) as binary data.
Word Coordinate
C+1 Xm (max. X value)
C+2 Y
0
C+3 X
1
C+4 Y
1
C+5 X
2
C+6 Y
2
↓↓
C+(2m+1) X
m
(max. X value)
C+(2m+2) Y
m
D0 000B Hex
D1 05F0 Hex
D2 0000 Hex
D3 0005 Hex
D4 0F00 Hex
D5 001A Hex
D6 0402 Hex
D25 05F0 Hex
D26 1F20 Hex
0000000000001011
15
00
x=S
X12
Y0
X1
Y1
Y2
X2
X12
Y12
Bit Bit
Content Coordinate
Output and input
both binary
(m–1 = 11: 12 line
segments)
↓↓ ↓
APR
D0
10
11
.
X
Y
$1F20
$0F00
$0726
$0402
(0,0)
$0005 $0014 $001A $05F0
(x,y)
Y0F00
0402 0F00–
001A 0005–
---------------------------------
0014 0015–()×+=
Ω 0726=
Ω 0F00 0086 000F )×(–=
Values are all hexadecimal (Hex).

Table of Contents

Other manuals for Omron SYSMAC CP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSMAC CP Series and is the answer not in the manual?

Omron SYSMAC CP Series Specifications

General IconGeneral
BrandOmron
ModelSYSMAC CP Series
CategoryComputer Hardware
LanguageEnglish

Related product manuals