1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 23 onicon.com
If this alarm is enabled and present on your meter, check the “Real-time Data” tab
to determine which turbine is not spinning as fast as the other. Then, the meter
should be removed, and the turbines should be inspected for damage or debris.
Be sure the meter is installed at the correct depth and orientation if this alarm is
present at initial installation.
Turbine Rotation Test tab
Turbine Rotation Test (Editable)
This parameter denes if the turbine rotation test is active, and what happens to
the operation of the meter if the test determines a problem with the turbines. The
Congurator provides the following options:
O – The turbine rotation test is disabled.
Alarm and Run – The turbine rotation test will be active in the background. If
a problem is detected, the relay output will close (if activated in the “Meter
Data” tab) and an alarm will be present in the “Status” tab. The meter will
continue to provide a frequency, scaled, and analog output even though it is
likely inaccurate because of a turbine problem.
Alarm and Zero Flow - The turbine rotation test will be active in the
background. If a problem is detected, the relay output will close (if activated
in the “Meter Data” tab) and an alarm will be present in the “Status” tab. The
meter will cease providing a ow rate signal on the frequency, scaled, and
analog outputs.
After changing this setting, press the “Set” button to accept the change.
Turbine Rotation Test enable/disable options.