1000 SERIES TURBINE METER CONFIGURATION UTILITY AND INSTALLATION GUIDE
ONICON Incorporated 727.447.6140 Page 24 onicon.com
Turbine Rotation Allowed Percent Dierence (Editable)
This parameter sets the allowed dierence in turbine rotation speed before an
alarm is enabled. The default value is 55.
Example with “Allowed Percent Dierence” set at 55:
• The “Status” tab reports that the top turbine frequency is 60 Hz, while
the bottom turbine is 40 Hz. The percent dierence in rotation is 33.33%.
Turbine rotation alarm is not triggered.
• The “Status” tab reports that the top turbine frequency is 60 Hz, while
the bottom turbine is 25 Hz. The percent dierence in rotation is 58.33%.
Turbine rotation alarm has the potential to be triggered (See “Turbine
Rotation Detect Time Sec” below).
After the parameter is changed, press “Set” to conrm the changes.
Turbine Rotation Detect Time Sec (Editable)
This parameter set the amount of time that the percent dierence in turbine
rotation must occur before an alarm is triggered. The default value is 120 sec.
This gives the meter a buer, before going into alarm, in case debris stopped the
turbine momentarily.
Example with “Allowed Percent Dierence” set at 55 and “Turbine Rotation
Detect Time Sec” set at 120:
The “Status” tab reports that the top turbine frequency is 60 Hz, while the
bottom turbine is 25 Hz. The percent dierence in rotation is 58.33%. Turbine
rotation alarm will be triggered after 120 seconds with the meter in this
state. If the turbine rotation % dierence falls below 55 before 120 seconds is
reached, the 120 second counter will reset, and no alarm will trigger.
After the parameter is changed, press “Set” to conrm the changes.
Turbine Rotation Reset Time Sec (Editable)
This parameter sets the time required for the turbine rotation alarm to disable
after a turbine rotation alarm has already been enabled. The default time is 10
seconds.
After the parameter is changed, press “Set” to conrm the changes.