SECTION 4 OPERATION
49
4.5.2.1 TIME BASED TRANSIENT EXAMPLE (continued)
NUMBER OF TRANSIENT EVENTS=1
(0 for infinite or 1-65535)
TRANSIENT AUTO RMS=ON
(Press +/- Key to Toggle Selection)
Press 1, ENTER, to cause only one transient event.
NUMBER OF TRANSIENT EVENTS=1
(0 for infinite or 1-65535)
TRANSIENT AUTO RMS=ON
(Press +/- Key to Toggle Selection)
Press STORE, to save Transient with AUTO RMS active or +/-, STORE to disable AUTO RMS.
The display now shows V/I METER.
V/I METER:
FREQ=400.0 Va=108.0 Vb=108.0 Vc=108.0
SENSE=INT Vab=187.1 Vbc=187.1 Vca=187.1
MANUAL MODE Ia=00.0 Ib=00.0 Ic=00.0
If the UPC was previously executing program #4, it will now be in MANUAL MODE, as indicated at the lower
left corner of the display, because program #4 has changed since it was EXECUTED. To use the newly
created transient you must first EXECUTE Program #4 again. Press PROGRAM, 4, ENTER, EXECUTE, to
execute the program.
V/I METER:
FREQ=400.0 Va=108.0 Vb=108.0 Vc=108.0
SENSE=INT Vab=187.1 Vbc=187.1 Vca=187.1
PROGRAM #4 Ia=00.0 Ib=00.0 Ic=00.0
Press TRANS to execute the transient.
This is a MIL-STD-704D under voltage time based transient (Figure 4.5.2.1).