22
11.2.3. Range and settings of thermal protection / nominal intensity of the contactors (class AC3)
Models 140 150 170 190 210
FTI
Range 24-32A 23-32A 30-40A 30-40A 37-50A
Adjustment 32A 32A 38A 38A 46A
FT2
Range 20-25A 23-32A 23-32A 30-40A 30-40A
Adjustment 22A 27A 32A 32A 32A
FT3
Range 24-32A 23-32A 23-32A 30-40A 37-50A
Adjustment 32A 32A 32A 38A 46A
FT4
Range 20-25A 23-32A 23-32A 30-40A 30-40A
Adjustment 22A 27A 27A 32A 32A
FTOF1-L
Range 2,5-4A 2,5-4A 6-10A 6-10A 6-10A
Adjustment 3,5A 3,5A 7A 7A 7A
FTOF1-H
Range 2,5-4A 2,5-4A 6-10A 6-10A 6-10A
Adjustment 3,5A 3,5A 7A 7A 7A
FTOF2-L
Range 2,5-4A 2,5-4A 2,5-4A 6-10A 6-10A
Adjustment 3,5A 3,5A 3,5A 7A 7A
FTOF2-H
Range 2,5-4A 2,5-4A 2,5-4A 6-10A 6-10A
Adjustment 3,5A 3,5A 3,5A 7A 7A
FTWP
Standard pump
Range 6-10A 6-10A 6-10A 6-10A 6-10A
Adjustment 6,4A 6,4A 6,4A 6,4A 6,4A
FTWP
High pressure pump
Range 9-14A 9-14A 9-14A 9-14A 9-14A
Adjustment 10,5A 10,5A 10,5A 10,5A 10,5A
Contactors
KOF1 / KOF1-L / KOF1-H 6A 6A 9A 9A 9A
KOF2 / KOF2-L / KOF2-H 6A 6A 6A 9A 9A
KWP1/2
Standard pump 9A 9A 9A 9A 9A
KWP1/2
High pressure pump 12A 12A 12A 12A 12A