82
Appendix Heat Pump Chiller 140-210
Start up form
Customer information:
Order number: ....................................................................... Job name: .............................................................................
Contractor: ............................................................................ Installation address: ..............................................................
Contact: .................................................................................
☎: ........................................................................................
Installer information:
Company: .............................................................................. Address: ................................................................................
Contact: ................................................................................. %: .........................................................................................
Commissioning information:
Company: .............................................................................. Address: ................................................................................
Contact: ................................................................................. %: .........................................................................................
Unit identifi cation:
140 150 170 190 210
Unit serial number: ................................................................
YES NO YES NO
Single pump All Seasons kit
Double pump Soft Starter
Buffer tank
Compressor 1-1 serial number: ............................................. Compressor 1-2 serial number: ............................................
Compressor 2-1 serial number: ............................................. Compressor 2-2 serial number: ............................................
Installation checking:
YES NO YES NO
Recommended free clearance Water connection, cleaning, rinsing, air bleed
Level installation Anti-frost protection of the water loop
Unit correctly mounted on supplied dampers Installation thermal load reaches at least 50%
Power supply compatible with unit specifi cations Mesh fi lter at the inlet of the unit
Supply cable is correctly sized Minimum water fl ow rate available
Ground cable is wired Flowswitch cut-out checked
Main electrical protection suits the unit Crankcases heaters are energized since 12 hours
All electrical connections are correctly tightened
Ground continuity on all pipes
Observations:
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................
....................................................................................................................................................................................................................................