EasyManua.ls Logo

Panasonic 140 - Page 43

Panasonic 140
84 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
43
Tasks per components Actions
Months
1 3 4 12 24
Recommended inspection
and maintenance interval
3.10 Check fi lter cleanliness Clean
3.11
Check that the hydraulic circuit is fi lled
properly
3.12
Check the condition of the expansion tank
(presence of excessive corrosion, or gas
pressure loss)
Replace if required
3.13 Check the water pump
If the unit has not been used for a long
time, manually rotate the pump shaft
and check that it turns freely.
For a unit equipped with a double
pump, it is recommended to switch
from one pump to the other every
month or to check that the pump
shaft turns freely to prevent the liners
sticking.
Change the pump liner after 15,000
hours running with anti-freeze or
25,000 hours running with water
3.14
Verify that low water pressure sensor works
perfectly
3.15
Record the water temperatures at the plate
heat exchanger inlet and outlet
4 - Electric circuit
4.1
Check the electrical voltage applied to the
unit, which must remain stable within the
tolerances specifi ed in the information plates
4.2
Check that the main supply cable is void of
alterations likely to impact the insulation
Replace if required
4.3 Check the grounding of the metallic structure Repair if required
4.4 Inspect the contacts Replace if required
4.5
Check that all electrical connections of the
device are tight
Tighten if required
✘✘
4.6
Check the thermal protection relays of the
motors
Replace if required
4.7
Check the nominal intensity and condition of
the fuses
4.8 Check the condition of the condensers
4.9
Clean the electrical cabinet with compressed
air to remove any dust or other contaminants
building up
✘✘
4.10 Check the motor windings are insulated
5 - Fan(s)
5.1
Check for lack of contamination, corrosion or
damage
Clean if required
5.2 Check proper fastening of the fan Tighten if required
5.3 Check the vanes to guarantee balancing Clean if required
5.4 Check the bearings for noise Repair if required
5.5
Check the condition of the grease and
greasers (unless permanently lubricated)
Re-grease if required (Lithium soap
grease DIN 51825-K3N for fans type
K, K1, K2)
T >
70°C
5.6 Check the condition of the fan motor
6 - Control
6.1 Check the condition of the alarms
Acknowledge them after taking them
into consideration
6.2 Check the operating set-points
6.3 Check the operation of all probes

Table of Contents