EasyManuals Logo

Panasonic CZ-KPY3A series Service Manual

Panasonic CZ-KPY3A series
693 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #286 background imageLoading...
Page #286 background image
1
1-276
Tubing Size
(A) Single type
Refrigerant tubing between the indoor and outdoor units should be kept as short as possible.
The lengths of the refrigerant tubes between the indoor and outdoor units are limited by the elevation difference
between the 2 units. During tubing work, try to make both the tubing length (L) and the difference in elevation (H1)
as short as possible.
H1
Single
Main tubing L
Outdoor unit type U-50PE1E5
U-60PEY1E5
U-71PEY1E5
Maximum allowable
tubing length
40 m 50 m
Charge-less tubing
length
(actual length)
3 – 30 m 3 – 20 m
Additional charge per 1 m
20 g 40 g
(B) Simultaneous operation multi (Twin)
NOTE
Because the indoor units run simultaneously, install them within the same room.
Table 1-1
ContentsmetI
Symbol Actual length (m)
Single Twin 50
60 – 71
single
71
twin
Allowable
tubing
lengths
Maximum
allowable
tubing length
One-way length of tubing
from outdoor unit to the most
distant indoor unit
L
L +
1
L +
2
40 50
40
Maximum
distribution
tubing length
Maximum length following
the first branch point (No. 1
distribution)
–
1,
2
15
Maximum branch tubing
length
Difference between the
maximum length and
minimum length in tubing
following the first branch point
–
1 >
2
1 –
2
10
Maximum difference between lengths of No. 1 distribution
tubing (double twin)
–
–
–
Maximum difference between lengths of No. 2 distribution
tubing (double twin)
–
–––
–
–
–
––
––
–
–
–
Maximum
allowable
height
difference
Maximum
indoor-
outdoor height
difference
If outdoor unit is higher
H1
30 30 30
If outdoor unit is lower
15
15 15
Maximum height difference between indoor units
H2
0.5
* For connection tubing sizes, refer to Table above.
1
2
H1
H2
Twin
CZ-P155BK1
Main
tubing L
Distribution joint
NOTE
For refrigerant tube branches, use the optional distribution joints.
For cautions on the use of the optional distribution joints, be sure to
refer to the provided instruction sheet.
Also, be careful to install them in the correct direction (orientation).
SM830231-02Singleī™€ę¬§å·ž.indb276SM830231-02Singleī™€ę¬§å·ž.indb276 2014/09/1913:21:452014/09/1913:21:45

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals