1-393
SELECTING THE INSTALLATION SITE
6. 4-Way Cassette 60Ɨ60 Type (Y2)
Indoor Unit
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly.
This may cause ā€œcondensationā€ on the air discharge ports,
causing them to spray or drip water.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner
of the room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
select a location where tubing and drain pipe have the
shortest run to the outdoor unit.
allow room for operation and maintenance as well as
unrestricted air flow around the unit.
install the unit within the maximum elevation difference
above or below the outdoor unit and within a total tubing
length (L) from the outdoor unit as detailed in the
installation manual packed with the outdoor unit.
allow room for mounting the remote controller about 1m
off the floor, in an area that is not in direct sunlight or in
the flow of cool air from the indoor unit.
4-Way Cassette 60Ɨ60 Type
The installation position must be able to support
a load four times the indoor unit weight.
WARNING
NOTE
Air delivery will be degraded if the distance from the floor to
the ceiling is greater than 3 m.
(Unit: mm)(Unit: mm)
Floor
Beam
1000 or more
500 or
more
Fig. 1-124
* If the height from the floor to ceiling exceeds three meters, air
flow distribution deteriorates and the effect is decreased.
Obstacles
500 or
more
500 or
more
300 or less
SM830231-02Singleī™€ę¬§å·ž.indb393SM830231-02Singleī™€ę¬§å·ž.indb393 2014/09/1913:22:052014/09/1913:22:05

Table of Contents

Other manuals for Panasonic CZ-KPY3A series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CZ-KPY3A series and is the answer not in the manual?

Panasonic CZ-KPY3A series Specifications

General IconGeneral
BrandPanasonic
ModelCZ-KPY3A series
CategoryAir Conditioner
LanguageEnglish

Related product manuals