1
1-462
1-13. Capacity Table
2. Heating Capacity Performance Data
ā¢
Combination of Multiple Unit
Ducted Type
TC :Cooling Capacity
IPT :Cooling Power Consumption
unit : kW
Outdoor air intake temp(°C W.B.)
Model
Power
Source
Ambient
Return
Air
-5°C 0°C 6°C 10°C 15°C
DB TC IPT TC IPT TC IPT TC IPT TC IPT
S-36PN1E5AĆ2
U-71PEY1E5
220V
230V
240V
50Hz
1 phase
16 5.6 2.20 6.1 2.30 8.3 2.70 9.4 2.93 10.6 3.17
20 5.5 2.32 6.0 2.43 8.1 2.84 9.1 3.09 10.2 3.33
24 5.2 2.39 5.7 2.50 7.8 2.93 8.7 3.18 9.8 3.43
S-50PN1E5AĆ2
U-100PEY1E5
(U-100PEY1E8)
220V
230V
240V
50Hz
1 phase
(3 phase)
16 13.4 4.48 13.9 4.05 14.9 3.87 13.9 2.94 15.6 3.08
20 12.4 4.74 12.9 4.29 13.8 4.10 12.9 3.11 14.5 3.26
24 11.6 4.82 12.1 4.36 12.9 4.17 12.0 3.16 13.5 3.31
S-60PN1E5AĆ2
U-125PEY1E5
(U-125PEY1E8)
220V
230V
240V
50Hz
1 phase
(3 phase)
16 14.5 5.03 15.2 4.55 16.2 4.35 15.1 3.30 17.0 3.45
20 13.5 5.32 14.0 4.81 15.0 4.60 14.0 3.49 15.7 3.65
24 12.6 5.41 13.1 4.89 14.0 4.67 13.1 3.55 14.7 3.71
S-71PN1E5AĆ2
U-140PEY1E8
220V
230V
240V
50Hz
3phase
16 16.7 5.52 17.2 5.43 17.3 4.91 17.3 4.33 17.3 3.66
20 15.5 5.84 15.9 5.74 16.0 5.20 16.0 4.58 16.0 3.87
24 14.5 5.93 14.9 5.84 15.0 5.28 15.0 4.65 15.0 3.94
SM830231-02īSingleī꬧å·.indbīīī462SM830231-02īSingleī꬧å·.indbīīī462 2014/09/19īīī13:22:252014/09/19īīī13:22:25