List of Item Codes (Some item codes cannot be set due to the type of models.)
retemaraPedoc metI
05 Silent level 1=Silent level1 2=Silent level2 3=Silent level3
07 Ignore capacity 0 = Disabled 1 = Ignores capacity ratio
0C Forced operation of
indoor unit drain pump
0 = Disable
1 = 2 hours stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
2 = 20 minutes stopped + 20 minutes operating
(regardless of whether the unit is running or stopped)
3 = Always operating
(regardless of whether the unit is running or stopped)
4 = XX minutes (Setting of Item code "2B") operating
when the unit change to thermo off or stop from thermo on.
5 = XX minutes (Setting of Item code "2B") operating
when the unit change to stop (regardless of whether the unit
was thermo on or thermo off).
6 = Doing the action 4 and 5.
7 = During cooling only, Doing the action 6.
0=Heat pump 1=Cooling onlyCooling onlyE0
12 Silent mode 0=Disable(at shipment) 1=At any times 2=Capacity priority
3=Timer setting 4=2+3
13 22 = 22 o'clock (at shipment)
14 00 = 00 minute (at shipment)
15 28 = 28 o'clock (at shipment)
16 00 = 00 minute (at shipment)
1A 40㧠㨪 130㧠, -1(no control)
1B 40㧠㨪 130㧠, -1(no control)
1D 40㧠㨪 130㧠, -1(no control)
2B
Operating time of indoor unit drain pump
Current control level
Demand 1 Current
Demand 1 Current
Silent mode finishinging time (minutes)
Silent mode finishinging time (hour)
Silent mode starting time (minutes)
Silent mode starting time (hour)
0=20minutesŽ1=30minutesŽ2=40minutes
3=50minutesŽ4=60minutes
* Figures in parentheses indicate the data at the time of shipment from the factory.