EasyManuals Logo

Panasonic FP2 Technical Manual

Panasonic FP2
68 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #16 background imageLoading...
Page #16 background image
General Specifications FP2 Multi-wire Link Unit
1-8
1.2 Specifications
1.2 Specifications
1.2.1 General Specifications
Item Descriptions
Ambient temperature
0to55
q
C/32 to 131
q
F
Storage temperature
-20 to +70
q
C/-4 to +158
q
F
Ambient humidity
30 to 85 % RH (non-condensing)
Storage humidity
30 to 85 % RH (non-condensing)
Breakdown voltage
500 V AC, 1 minute between external terminal and frame
ground terminal
Insulation resistance
100 M
Ω
or more (measured with a 500 V DC megger testing)
between external terminal and frame ground terminal
Vibration resistance
10 to 55 Hz, 1 cycle/min: double amplitude of 0.75 mm/
0.030 in., 10 min on 3 axes
Shock resistance
98 m/s
2
or more, 4 times on 3 axes
Noise immunity
1,000 Vp-p with pulse widths 50 ns and 1
μ
s
(based on in-house measurements)
Operating conditions
Free from corrosive gases and excessive dust
Current consumption
220 mA or less (at 5 V DC) (
*
Note)
Weight
A
pprox.
110 g/3.880 oz
.
Note
For information concerning restrictions on current consumption,
refer to section 1.4.1.

Table of Contents

Other manuals for Panasonic FP2

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP2 and is the answer not in the manual?

Panasonic FP2 Specifications

General IconGeneral
BrandPanasonic
ModelFP2
CategoryController
LanguageEnglish

Related product manuals