Parts and Its Functions FP2 Multi-wire Link Unit
2-8
2.2 Switch Settings
2.2.2 Mode Selector Switches (1)
Operation mode
Terminal station: With MEWNET, the units at both ends of the network must be
specified as “terminal stations”.
(Front)
When the unit is shipped from the factory, all switches are set to the “OFF” position.
Setting contents
o.
em
W mode W2 mode F mode
O
eration
OFF PC link mode
Operation stops if a
communication error occurs.
mode
ON Not PC link mode
Operation continues if a
communication error occurs.
2
3
4
Not used
— — —
5
6
7
Terminal
Set to terminal
station
ON OFF
8
station
Not set to terminal
station
ON OFF
.
Notes
D
The settings of the mode selector switches (1) and (2) should
always be changed with the power off. The setting will be ef-
fective the next time that the power is turned on. (If the setting
is changed with the power on, be aware that the setting in ef-
fect when the power was turned on will remain effective.)
D
Only the settings of the mode selector switches (1) No. 7 and
No. 8 (terminal station settings) will be effective at the instant
that they are changed.