1-15
Communication Parameters Settings
The example of communication settings of GT and PLC is shown below.
Setting Values for GT (Set in the configuration setting of GTWIN.)
Item
Setting
PLC Unit No.
0
Baud Rate
19200bps
Data Length
8
Stop Bits
1
Parity
Odd
Sum Check
Yes
*GT series supports the format 4 of QnA compatible 4C frame.
Setting Values for PLC (Serial communication module)
Item
Setting
Station Number
0
Baud Rate
19.2 Kbps
Data Length
8
Stop Bits
1
Parity
Odd
Sum Check
Check
Interface
RS232C
Use Serial Communication
Check
Online change
Enable