4-2
4.1 Allen-Bradley SLC500 MicroLogix Series
PLC model selection
Select "Allen-Bradley SLC500 MicroLogix Series".
Usable devices vary according to the version of GTWIN.
Usable devices (When the version of GTWIN is Ver.2.96 or later)
Bit/Word Device
No.
Bit Device
Bit
B 3:0/0~B 255:255/15
Input
I: 0.0/0~I: 30.255/15
Output
O: 0.0/0~O: 30.255/15
Status
S 0/0~S 164/15
Timer (Effective bit)
T/EN 3:0~T/EN 255:255
Timer (Clock bit)
T/TT 3:0~T/TT 255:255
Timer (Completion bit)
T/DN 3:0~T/DN 255:255
Counter (Up counter)
C/CU 3:0~C/CU 255:255
Counter (Down counter)
C/CD 3:0~C/CD 255:255
Counter (Completion bit)
C/DN 3:0~C/DN 255:255
Counter (Overflow bit)
C/OV 3:0~C/OV 255:255
Counter (Underflow bit)
C/UN 3:0~C/UN 255:255
Counter (Accumulator update bit)
C/UA 3:0~C/UA 255:255
Integer
N 7:/0~N 255:255/15
Control (Effective bit)
R/EN 6:0~R/EN 255:255
Control (Unload effective bit)
R/EU6:0~R/EU 255:255
Control (Completion bit)
R/DN 6:0~R/DN 255:255
Control (Stack empty bit)
R/EM 6:0~R/EM 255:255
Control (Error bit)
R/ER 6:0~R/ER 255:255
Control (Unload bit)
R/UL 6:0~R/UL 255:255
Control (Prohibition bit)
R/IN 6:0~R/IN 255:255
Control (Detection bit)
R/FD 6:0~R/FD 255:255
Word Device
Bit
B 3:0~B 255:255
Input
I: 0.0~I: 30.255
Output
O: 0.0~O: 30.255
Status
S 0~S 164
Timer (Setting value)
T.ACC 3:0~T.ACC 255:255
Timer (Current value)
T.PRE 3:0~T.PRE 255:255
Counter (Setting value)
C.ACC 3:0~C.ACC 255:255
Counter (Current value)
C.PER 7:0~C.PER 255:255
Integer
N 7:0~N 255:255
ASCII
A 8:0~A 255:255
Control (Position)
R.POS 6:0~C.POS 255:255
Control (Length)
R.LEN 6:0~R.LEN 255:255
Double Word Device
Floating decimal point
F 8:0~F 255:255
Long word (2-word integer)
L 9:0~C.PER 255:255
Character string Device
Character string
ST 9:0~ST 255:255