- App. 65 -
Appendixes
<Notes>
1. The automatic offset adjustment mode is not effective for the position control mode.
2. If the input voltage is over the adjustment range ( ±25% of the maximum input voltage), the mode cannot
work (an error occurs). Make sure that the input voltage is 0V.
3. If the value of Pr52 produced by the mode (i.e. the result of the offset adjustment) is not downloaded to
EEPROM before turning off the power, the value will be lost (the previous value remains). If you want to
continue to use the new value, download it to EEPROM before turning off the power.
Alarm Clear Mode
Clearing an alarm using the LED touch panel is the same as removing the trip status by using the alarm clear
signal (A-CLR).
Procedure
1) Select the alarm clear mode (refer to page 39 in Appendix). will appear.
Press SET button to display
2) The mode is ready for
execution.
SET
<Notes>
If one of the errors shown below is occurring, the trip status is not removed, and
appears.
In this case, remove the error by turning off the power, removing the cause and turning on the power again.
Over-current, overheat, encoder A/B phase error, encoder communication error, encoder disconnection, en-
coder communication data error, EEPROM parameter error, EEPROM check code error, absolute single-turn
counter error, absolute multi-turn counter error and Other error
The mode is started.
The clearing operation
will complete instanta-
neously.
Clearing completed Error
Keep pressing UP
button (for about three sec-
onds). The number of short
bars (-) will increase.