Loading...
4-16
VRF SYSTEMS Indoor Unit Specifi cations
1
2
3
4
5
6
7
8
9
1. 4-Way Cassette Type (U1 Type)
Indoor unit ( K )
MODEL No.
S-160MU1E5A
Power source
220 - 230 - 240 V, single-phase, 50/60 Hz
Controller P.C.B. Ass'y
A73C5900 (Microprocessor)
Fan (Number...diameter)
Turbo (1...ø490)mm
Fan motor
SIC-72FW-D892-4...90 WWModel...Nominal output
Power source 280 VDC
8P...630rpmNo. of pole...r.p.m. (230V)
VAC, μFRun capacitor
Safety device
overcurrent, rotating signal detection, fuse
Electronic expansion valve
Coil UKV-A152
Coil resistance (at 20°C)
ORG – GRY : 46 YEL – GRY : 46
RED – GRY : 46 BLK – GRY : 46
Valve body UKV-30D33
Heat exchanger
Aluminium plate fin / Copper tubeCoil
2...1.21mmRows...fin pitch
mFace area
2
0.522
Panel
Model No. CZ-KPU21
MSBPC20A20Auto louver motor
Coil resistance
300 Ω ± 7% / phase
Drain pump
PMD-12D13ST-1
DC 13 V, 4.2 WV, WRated
850 mm, 400 cc/min
Drain piping rise height from unit bottom, capacity