4-73
VRF SYSTEMS Indoor Unit Specifi cations
5. Wall Mounted Type (K1 Type)
Unit specifications (A)
MODEL No.
Indoor Unit S-45MK1E5A
POWER SOURCE
220 - 230 - 240 V, single-phase, 50/60 Hz
PERFORMANCE TEST CONDITION
ISO15042 / AS / NZS3823 / EN14511 / EN12102
PERFORMANCE
Cooling Heating
Capacity
kW 4.5 5.0
BTU / h 15,000 17,000
Air circulation (Hi / Me / Lo) m
3
/ h 720 / 630 / 510
Moisture removal (High) Liters / h 1.6 –
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 - 264 198 - 264
Running amperes A 0.27 0.26 0.23 0.27 0.26 0.23
20 20 21 20 20 21
34 33 38 34 33 38
1111 1 1
Power input W
Power factor %
Max. starting amperes A
FEATURES
Controls Microprocessor
Timer ON / OFF Timer (Max. 72 h)
Fan speeds 3 and Automatic control
Air fi lter Washable, easy access
Refrigerant control Electronic expansion valve
Operation sound (
Hi / Me / Lo
) dB-A 38 / 34 / 30
Refrigerant tubing connections Flare type
Refrigerant tube
diameter
Liquid tube mm (in.) 6.35 (1 / 4)
Gas tube mm (in.) 12.7 (1 / 2)
Drain connection 13 A, OD18 mm
Remote controller Optional (Wired / Wireless)
Refrigerant tubing kit / Accessories Optional / Hanging wall bracket
Color (Approximate value) Munsell N9.1
DIMENSIONS & WEIGHT
Unit dimensions
Package dimensions
Unit dimensions
Height mm (in.) 300 (11-13 / 16) 310 (12-7 / 32)
Width mm (in.) 1065 (41-15 / 16) 1140 (44-7 / 8)
Depth mm (in.) 230 (9-1 / 16) 380 (14-31 / 32)
Net weight kg (lbs.) 13 (29)
Shipping weight kg (lbs.) 17 (38)
Shipping volume m
3
(cu.ft) 0.13 (4.6)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Rated conditions
Cooling: Indoor air temperature 27°C DB / 19°C WB; Outdoor air temperature 35°C DB
Heating: Indoor air temperature 20°C DB; Outdoor air temperature 7°C DB / 6°C WB
5-1. Specifi cations