2-59
Design of VRF SYSTEM
1
2
3
4
5
6
7
8
9
4. Optional Parts
4-3. External Electronic Expansion Valve Kit for Indoor Unit
CZ-P56SVK2, CZ-P160SVK2 (for R410A)
Precautions in this manual are given in the form of “Warnings” or “Cautions.
” Both types of precautions contain important information related to your safety, the safety of users, and the correct operation,
installation, or maintenance of the air conditioning system. Be sure to carefully observe all relevant precautions.
This symbol refers to a hazard or unsafe practice which can result in severe personal injury or death.
This symbol refers to a hazard or unsafe practice which can result in personal injury or product or property
damage.
WARNING
CAUTION
This external electronic expansion valve is compatible with the refrigerants listed below.
R410A, R407C, R22
Checking Parts
Please check these parts below that came in the box.
1
2
3
4
5
1
2
1
2
1
Large: 2
Small: 4
Q'tyShapeDescription
External electronic
expansion valve
(Extension cord 8 m)
Flare insulator
Clamp
(Large: 350 mm,
Small: 200 mm)
Installation manual
6
Insulating tape
Connector-converter
cable
White
(heat resisting)
Installation Procedure
1. Positioning for Installation
The valve should be connected to the liquid tube.
Determine the position for installation referring to the
diagram of outer dimensions. (Fig. 2-163)
Refrigerant-flow noise may occur from the external
electronic expansion valve. As a guide, the distance
from the indoor unit should be a minimum of 5 m,
but less than 8 m. (Install away from locations where
strictly quiet operation is required.) If this distance is
unavailable, install inside the ceiling or in another
location where noise insulation is possible.
This is a functional component, and therefore may
require inspection and replacement.
Consider this when deciding the installation location.
(For example, place near an inspection port, or provide one.)
This valve is for indoor use. Do not install the valve outdoors.
Extension cord (8m) Connection port B
Connection port B
Fig. 2-163 Diagram of outer dimensions
Unit: mm
(205)
(275)
Type
(70)
A
Indoor side Outdoor side
56
160
A (mm)
325
360
B (mm)
ø6.35
ø9.52
TDxxxxxx-002WAYVRF.indb59TDxxxxxx-002WAYVRF.indb59 2014/01/3017:52:322014/01/3017:52:32