2-10
Design of VRF SYSTEM
2. SELECTING THE INSTALLATION SITE
2-2. 4-Way Cassette 60×60 (Y2 type)
AVOID:
areas where leakage of flammable gas may be expected.
places where large amounts of oil mist exist.
direct sunlight.
locations near heat sources which may affect the
performance of the unit.
locations where external air may enter the room directly.
This may cause “condensation” on the air discharge ports,
causing them to spray or drip water.
locations where the remote controller will be splashed with
water or affected by dampness or humidity.
installing the remote controller behind curtains or furniture.
locations where high-frequency emissions are generated.
DO:
select an appropriate position from which every corner of
the room can be uniformly cooled.
select a location where the ceiling is strong enough to
support the weight of the unit.
WARNING
The installation position must be able to support a load four times the indoor unit weight.
select a location where tubing and drain pipe have the shortest run to the outdoor unit.
allow room for operation and maintenance as well as unrestricted air flow around the unit.
install the unit within the maximum elevation difference above or below the outdoor unit and within a total tubing length (L)
from the outdoor unit as detailed in the Installation Instructions provided with the outdoor unit.
allow room for mounting the remote controller about 1m off the floor, in an area that is not in direct sunlight or in the flow
of cool air from the indoor unit.
NOTE
Air delivery will be degraded if the distance from the floor to the ceiling is greater than 3 m.
* If the height from the floor to ceiling exceeds three meters,
air flow distribution deteriorates and the effect is decreased.
Fig. 2-13
Only for Y2 Type
Obstacles
Floor
2.5 m – 3 m
1 m or
more
50cm
or more
Beam
30 cm or less
50cm
or more
50cm
or more