4-51
VRF SYSTEMS Indoor Unit Specifi cations
3. 4-Way Cassette 60×60 Type (Y2 Type)
Indoor unit (A)
MODEL No.
S-15MY2E5A
Power source
220 - 230 - 240 V, single-phase, 50/60 Hz
Controller P.C.B. Ass'y
A73C7569 (CR-22MY2E5 : Microprocessor)
Fan (Number...diameter)
mm Turbo (1...ø333.4, L147)
Fan motor
Model...Nominal output W NFD-62FW-F240-2...40 W
Power source 325 VDC
No. of pole...r.p.m. (230V, High) rpm 8P...580 / 590
Coil resistance
(Ambient temperature 20°C)
–
Run capacitor VAC, µF –
Safety device
Electronic expansion valve
Coil CAM-MD12MS
Coil resistance (at 20°C)
WHT – RED : 46 ± 5% ORG – RED : 46 ± 5%
YEL –
RED : 46 ± 5% BLU – RED : 46 ± 5%
Valve body CAM-BD18MS-2
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fi n pitch mm 2...1.4
Face area m
2
0.263
Panel
Model No. CZ-KPY3A
Auto louver motor MP24Z
Coil resistance (at 25°C)
250 ± 7.5%
Drain pump
Rated V, W AC 230 V, 12 W
Height from unit bottom & capacity 850 mm, 400 cc/min
3-2. Major Component Specifi cations