4-77
VRF SYSTEMS Indoor Unit Specifi cations
1
2
3
4
5
6
7
8
9
5. Wall Mounted Type (K1 Type)
5-2. Major Component Specifi cations
Indoor unit (A)
MODEL No.
S-45MK1E5A
Power source
220 - 230 - 240 V, single-phase, 50/60 Hz
Controller P.C.B. Ass'y
CR-K186XH (Microprocessor)
Fan (Number...diameter)
mm Cross-fl ow ø100 / L838
Fan motor
Model...Nominal output W SIC-39CVL-D847-10...47 W
Power source 220 - 230 - 240 V / single-phase / 50 Hz
No. of pole...r.p.m. (230V, High) rpm 8P... 1,650
Electronic expansion valve
Coil UKV-A052
Coil resistance (at 20°C)
ORG – GRY : 46 YEL – GRY : 46
RED – GRY : 46 BLK – GRY : 46
Valve body UKV-25D32
Heat exchanger
Coil Aluminium plate fin / Copper tube
Rows...fi n pitch mm 2...1.3
Face area m
2
0.325
TD831172-00VRFSYSINDOOR.indb77TD831172-00VRFSYSINDOOR.indb77 2014/04/2416:49:282014/04/2416:49:28