Installing the Drive 3-63
DC590+ DRV Series DC Digital Drive
Installing the Fan (Frame 7)
Refer to Appendix E: “Technical Specifications” - Cooling Fans.
The fan unit supplied should be installed on the cubicle, with or without ducting (refer to the Installation Drawing). The drive is force-cooled using the
fan units supplied with the drive. As a general rule allow at least 150mm (6 inches) of clear space above and below the drive for free air flow. We
suggest the cubicle has an air inlet at the base of the cubicle equivalent to 0.37m
2
(4ft²), variable depending upon the filter type used, to allow the
maximum throughput of air.
The fan assembly provided is permanently wired as shown below.
Figure 3-22 Frame 7 Fan Wiring Diagram
115V ac
1
2
3
4
PE/GRD
L
N
115V ac + 10%
50/60Hz
230V ac
1
2
3
4
PE/GRD
L
N
230V ac + 10%
50/60Hz
L
N
L
N
L
N
L
N
4.5A
2.25A
PE/GRD
FN4
FN3
FN2
FN1