D-76 Programming
DC590+ DRV Series DC Digital Drive
LOGIC FUNC
Parameter Tag Range
INPUT A
780, 785, 790, 795, 800, 805, 810, 815, 820,
825
FALSE / TRUE
General purpose logic input.
INPUT B
781, 786, 791, 796, 801, 806, 811, 816, 821,
826
FALSE / TRUE
General purpose logic input.
INPUT C
782, 787, 792, 797, 802, 807, 812, 817, 822,
827
FALSE / TRUE
General purpose logic input.
TYPE
783, 788, 793, 798, 803, 808, 813, 818, 823,
828
See below
The operation to be performed on the three inputs to produce the output value. The operations that can be selected are:
0: NOT(A)
1: AND(A,B,C)
2: NAND(A,B,C)
3: OR(A,B,C)
4: NOR(A,B,C)
5: XOR(A,B)
6: 0-1 EDGE(A)
7: 1-0 EDGE(A)
8: AND(A,B,!C)
9: OR(A,B,!C)
10: S FLIP-FLOP
11: R FLIP-FLOP
12: LATCH
13: SWITCH
14: (A AND B) OR C
15: (A OR B) AND C
OUTPUT
784, 789, 794, 799, 804, 809, 814, 819, 824,
829
FALSE / TRUE
The result of performing the selected operation on the inputs.